Reer Safety MOSAIC MI8O2 (1100010) | Get A Quote Today
+91 79955 44066 sales@indmall.in

MOSAIC MI8O2C: 1100110 - Reer PL e Safety Level Controllers

Technical Specifications of Reer 2 Status PNP Output Safety Controllers MOSAIC MI8O2 1100010:

SpecValue
Safety LevelPL e
Safety Inputs8 digital inputs
ConnectionsRemovable terminal blocks. screw contacts
Safety Outputs2 OSSD pairs (400 mA)

Reer PL e Safety Level Controllers MOSAIC MI8O2C, 1100110 Technical Specifications:

SpecificationValue
Safety levelPL e
Safety inputs8 digital inputs
Safety level (SIL / PL)SIL 3 - SILCL 3 - PL e - Cat. 4
Operating temperature (°C)- 10 ... 55
SignallingLEDs indication for operating status and fault diagnosis. LED indication of the: inputs. OSSD outputs and status outputs condition
Safety output type2 OSSD PNP (400 mA at 24 VDC) with protection against short circuit. overload and reverse polarity
ConnectionsRemovable terminal blocks. screw contacts
MTTFD (ISO13849) years30 ... 100
PFHD (IEC 61508)5.68E-09
Safety outputs2 OSSD pairs (400 mA)
Status outputs2 PNP (100 mA)
Test outputs4
Storage temperature (°C)-20 ... +85
MSC connector providedYes
Connection with MSC BUSYes
Start/Restart inputs and EDM2
Housing for MCM
USB input
Packaging dimensions HxLxW (mm)36 x 127 x 113
Product classC
Custom tariff85371091
Power supply (VDC)24 ± 20%
Dimensions HxWxD (mm)108 x 22.5 x 114.5
Degree of protectionIP20 for housing - IP2X for terminal block
Fastening35 mm DIN rail fastening according to EN 50022-35 standard
Gross weight (g)185.4
Please speak to our Technical Engineer for Reer 2 Status PNP Output Safety Controllers MOSAIC MI8O2 part no: 1100010 at attractive prices. Technical Specs Summary of MOSAIC MI8O2, 1100010 includes provide top-tier protection with PL e safety level, featuring 8 digital inputs, SIL 3 - SILCL 3 - PL e - Cat. 4 certification. Operating efficiently between - 10 ... 55, these controllers offer clear LEDs indication for operating status and fault diagnosis. LED indication of the: inputs. OSSD outputs and status outputs condition. Equipped with 2 OSSD PNP (400 mA at 24 VDC) with protection against short circuit. overload and reverse polarity, they ensure reliable safety outputs. The Removable terminal blocks. screw contacts, coupled 2 OSSD pairs (400 mA) and 4 test outputs, add to their robustness. These controllers are IP20 for housing - IP2X for terminal blockprotected enclosures, designed for 35 mm DIN rail fastening according to EN 50022-35 standard. With a compact design of 108 x 22.5 x 114.5 and a gross weight of 185.4 g, they offer reliable performance for industrial applications. Match Your Needs with a Quote for your requirement of Reer 2 Status PNP Output Safety Controllers. We lead with pricing that's more favorable and support that's more attentive than other Suppliers & Traders.