Technical Specifications of Schneider 30 kW VFD ATV630D30N4Z:

SpecValue
Shock Resistance15 gn for 11 ms conforming to IEC 60068-2-27
Connection TypeRJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial
Motor Power KW30 kW (normal duty)22 kW (heavy duty)
Switching Frequency2...12 kHz adjustable4...12 kHz with derating factor

Schneider 30 kW VFD ATV630D30N4Z Technical Specifications:

SpecificationValue
Maximum input current53.3 A
Electrical connectionControl: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16Line side: screw terminal 25...50 mm²/AWG 4...AWG 1Motor: screw terminal 25...50 mm²/AWG 4...AWG 1
Power dissipation in WNatural convection: 93 W at 380 V, switching frequency 4 kHzForced convection: 640 W at 380 V, switching frequency 4 kHz
Overvoltage categoryIII
Net weight25.8 kg
Shock resistance15 gn for 11 ms conforming to IEC 60068-2-27
Relay output typeConfigurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Frequency resolutionDisplay unit: 0.1 HzAnalog input: 0.012/50 Hz
Output voltage<= power supply voltage
Insulation resistance> 1 MOhm 500 V DC for 1 minute to earth
Product or component typeVariable speed drive
Discrete output typeRelay outputs R1A, R1B, R1C 250 V AC 3000 mARelay outputs R1A, R1B, R1C 30 V DC 3000 mARelay outputs R2A, R2C 250 V AC 5000 mARelay outputs R2A, R2C 30 V DC 5000 mARelay outputs R3A, R3C 250 V AC 5000 mARelay outputs R3A, R3C 30 V DC 5000 mA
Nominal switching frequency4 kHz
SupplyExternal supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protectionInternal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
Maximum transient current67.7 A during 60 s (normal duty)69.5 A during 60 s (heavy duty)
Relay output number3
Type of polarizationNo impedance
Product specific applicationProcess and utilities
Volume of cooling air240 m3/h
Connector typeRJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial
Refresh timeRelay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Method of accessSlave Modbus TCP
Product destinationAsynchronous motorsSynchronous motors
Minimum switching currentRelay output R1, R2, R3: 5 mA at 24 V DC
Accuracy+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Ambient air temperature for storage-40…70 °C
Motor power hp40 hp normal duty30 hp heavy duty
Transmission rate10, 100 Mbits4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Maximum THDI<48 % from 80...100 % of load conforming to IEC 61000-3-12
Height597 mm
Type of coolingForced convection
Motor power kW30 kW (normal duty)22 kW (heavy duty)
Number of Units in Package 11
Physical interfaceEthernet2-wire RS 485
Switching frequency2...12 kHz adjustable4...12 kHz with derating factor
Apparent power38.2 kVA at 480 V (normal duty)29.8 kVA at 480 V (heavy duty)
StandardsUL 508CIEC 61800-3IEC 61800-3 environment 1 category C2EN/IEC 61800-3 environment 2 category C3IEC 61800-5-1IEC 61000-3-12IEC 60721-3IEC 61508IEC 13849-1
Operating positionVertical +/- 10 degree
Discrete input logicPositive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Package 2 Length-
Range of productAltivar Process ATV600
[Us] rated supply voltage380...480 V - 15...10 %
Permissible temporary current boost1.1 x In during 60 s (normal duty)1.5 x In during 60 s (heavy duty)
MarkingCE
Analogue input number3
Asynchronous motor control profileVariable torque standardOptimized torque modeConstant torque standard
Enclosure mountingWith heat sink
IsolationBetween power and control terminals
Ambient air temperature for operation-15…50 °C (without derating)50…60 °C (with derating factor)
Vibration resistance1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-61 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Supply frequency50...60 Hz - 5...5 %
Acceleration and deceleration rampsLinear adjustable separately from 0.01...9999 s
Analogue output number2
Pollution degree2
Request a quote for the Schneider 30 kW VFD ATV630D30N4Z at economical prices. This VFD, part of the Altivar Process ATV600 range, is ideal for process and utility applications. Key specifications include a maximum input current of 53.3 A and a frequency resolution of 0.1 Hz on the display unit, with 0.012/50 Hz on the analog input. The output voltage is up to the power supply voltage, with a maximum transient current of 67.7 A for 60 seconds in normal duty and 69.5 A in heavy duty. It supports motor power of 40 hp for normal duty and 30 hp for heavy duty, standing at a height of 597 mm and featuring Ethernet and a 2-wire RS 485 interface. The switching frequency is adjustable from 2...12 kHz, or 4...12 kHz with a derating factor. Operating at a rated supply voltage [Us] of 380...480 V with a -15...+10 % tolerance and a supply frequency of 50...60 Hz within -5...+5 % tolerance, it reaches a maximum output frequency of 500 kHz and is securely installed in a cabinet mount. Reach out now for a tailored quote on the Schneider 30 kW VFD and experience our competitive pricing and exceptional support, setting us apart from other competitors.