TM241CEC24T: Schneider Modicon M241 CAN Master Controller
Tecnhical specifications of Schneider Modicon M241 CAN Master Controller TM241CEC24T 0lq4939ea@38m:
Spec | Value |
---|---|
Standards | ANSI/ISA 12-12-01CSA C22.2 No 142CSA C22.2 No 213IEC 61131-2:2007Marine specification (LR, ABS, DNV, GL)UL 508 |
Supply voltage limits | 20.4…28.8 V |
IP degree of protection | IP20 with protective cover in place |
Power consumption in W | 32.6…40.4 W (with max number of I/O expansion module) |
Ambient air temperature for operation | -10…50 °C (vertical installation)-10…55 °C (horizontal installation) |
Schneider Modicon M241 CAN Master Controller TM241CEC24T Technical Specifications:
Specification | Value |
---|---|
Insulation | Between supply and internal logic at 500 V ACNon-insulated between supply and groundBetween input and internal logic at 500 V ACNon-insulated between inputsBetween fast input and internal logic at 500 V ACBetween output and internal logic at 500 V ACNon-insulated between outputsBetween fast output and internal logic at 500 V AC |
Power consumption in W | 32.6…40.4 W (with max number of I/O expansion module) |
Port Ethernet | 10BASE-T/100BASE-TX - 1 port(s) copper cable |
Output voltage limits | 30 V DC |
Transmission rate | 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS4851.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232480 Mbit/s for bus length of 3 m for USB10/100 Mbit/s for Ethernet1000 kbit/s for bus length of 20 m for CANopen800 kbit/s for bus length of 40 m for CANopen500 kbit/s for bus length of 100 m for CANopen250 kbit/s for bus length of 250 m for CANopen125 kbit/s for bus length of 500 m for CANopen50 kbit/s for bus length of 1000 m for CANopen20 kbit/s for bus length of 2500 m for CANopen |
Voltage state 0 guaranteed | <= 5 V for input |
Range of product | Modicon M241 |
Maximum output frequency | 20 kHz for fast output (PWM mode)100 kHz for fast output (PLS mode)1 kHz for output |
Discrete output current | 0.5 A for transistor output (Q0...Q9)0.1 A for fast output (PTO mode) (Q0...Q3) |
Response time | 50 µs turn-on, I0...I13 terminal(s) for input50 µs turn-off, I0...I13 terminal(s) for input<= 2 µs turn-on, I0...I7 terminal(s) for fast input<= 2 µs turn-off, I0...I7 terminal(s) for fast input<= 34 µs turn-on, Q0...Q9 terminal(s) for output<= 250 µs turn-off, Q0...Q9 terminal(s) for output<= 2 µs turn-on, Q0...Q3 terminal(s) for fast output<= 2 µs turn-off, Q0...Q3 terminal(s) for fast output |
Surge withstand | 1 kV power lines (DC) common mode conforming to IEC 61000-4-51 kV shielded cable common mode conforming to IEC 61000-4-50.5 kV power lines (DC) differential mode conforming to IEC 61000-4-51 kV relay output differential mode conforming to IEC 61000-4-51 kV input common mode conforming to IEC 61000-4-51 kV transistor output common mode conforming to IEC 61000-4-5 |
Shock resistance | 15 gn for 11 ms |
Protection type | Short-circuit protectionShort-circuit and overload protection with automatic resetReverse polarity protection for fast output |
Supply voltage limits | 20.4…28.8 V |
Communication port protocol | Non isolated serial link: Modbus master/slave |
Vibration resistance | 3.5 mm at 5…8.4 Hz on symmetrical rail3 gn at 8.4…150 Hz on symmetrical rail3.5 mm at 5…8.4 Hz on panel mounting3 gn at 8.4…150 Hz on panel mounting |
Voltage state 1 guaranteed | >= 15 V for input |
Discrete output voltage | 24 V DC for transistor output |
Standards | ANSI/ISA 12-12-01CSA C22.2 No 142CSA C22.2 No 213IEC 61131-2:2007Marine specification (LR, ABS, DNV, GL)UL 508 |
Discrete input current | 5 mA for input10.7 mA for fast input |
Relative humidity | 10…95 %, without condensation (in operation)10…95 %, without condensation (in storage) |
Ambient air temperature for operation | -10…50 °C (vertical installation)-10…55 °C (horizontal installation) |
Discrete input voltage | 24 V |
Ambient air temperature for storage | -25…70 °C |
IP degree of protection | IP20 with protective cover in place |
Get A Quote for Schneider Modicon M241 CAN Master Controller TM241CEC24T at the best price. Here are the brief Technical Specifications of TM241CEC24T are Modicon M241 range, designed for efficient industrial automation. The sensor supports both Sink or source discrete input logic and operates with a power consumption of 32.6…40.4 W (with max number of I/O expansion module). The output voltage limits are 30 V DC, ensuring reliable performance. With a compact depth of 95 mm, it fits seamlessly into various setups. The discrete input voltage type is DC, and the supply voltage limits range from 20.4…28.8 V, providing flexibility in power management. The sensor handles inrush currents of up to 50 A and operates at altitudes up to 0...2000 m, with a storage altitude capacity of up to 0…3000 m. It supports a discrete input voltage of 24 V and can be stored in ambient air temperatures ranging from -25…70 °C. It's Time to get a Quote for your requirement of Schneider Modicon M241 CAN Master Controller. We guarantee unmatched pricing and unparalleled support compared to other Distributors.