LC1G330LSEA | Schneider AC-3 440V High Power Contactor
+91 79955 44066 sales@indmall.in

LC1G330LSEA: Schneider AC-3 440V High Power Contactor

Technical Specifications of Schneider AC-3 440V High Power Contactor LC1G330LSEA:

SpecValue
Power Dissipation Per Pole30 W AC-1 - Ith 440 A16 W AC-3 - Ith 330 A
Range of ProductTeSys Giga
Pole Contact Composition3 NO
Connection TerminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end

Schneider AC-3 440V High Power Contactor LC1G330LSEA Technical Specifications:

SpecificationValue
Device short nameLC1G
Power dissipation per pole30 W AC-1 - Ith 440 A16 W AC-3 - Ith 330 A
Ambient air temperature for operation-25…60 °C
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz<= 460 V DC
Range of productTeSys Giga
Rated breaking capacity2940 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Maximum operating rate600 cyc/h AC-3600 cyc/h AC-3e300 cyc/h AC-1150 cyc/h AC-4
Width140 mm
Poles description3P
Utilisation categoryAC-1AC-3AC-3eAC-4AC-5aAC-5bAC-6aAC-6bAC-8bAC-8aDC-1DC-3DC-5
ColourDark grey
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C)Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Motor power hp100 hp at 200/208 V 60 Hz125 hp at 230/240 V 60 Hz250 hp at 460/480 V 60 Hz300 hp at 575/600 V 60 Hz
Height290 mm
Mechanical durability8 Mcycles
[Ie] rated operational current440 A (at <40 °C) at <= 1000 V AC-1330 A (at <60 °C) at <= 440 V AC-3
Operating time40...70 ms closing15...50 ms opening
Pole contact composition3 NO
Ambient air temperature for storage-60…80 °C
Product or component typeContactor
[Uc] control circuit voltage200...500 V AC 50/60 Hz200...500 V DC
Tightening torque35 N.m
Depth226 mm
Associated fuse rating400 A aM at <= 440 V for motor250 A aM at <= 690 V for motor500 A gG at <= 690 V
[Icw] rated short-time withstand current2.65 kA - 10 s1.8 kA - 30 s1.3 kA - 1 min0.9 kA - 3 min0.75 kA - 10 min
Motor power kW90 kW at 230 V AC 50/60 Hz (AC-3e)160 kW at 400 V AC 50/60 Hz (AC-3e)160 kW at 415 V AC 50/60 Hz (AC-3e)185 kW at 440 V AC 50/60 Hz (AC-3e)200 kW at 500 V AC 50/60 Hz (AC-3e)220 kW at 690 V AC 50/60 Hz (AC-3e)185 kW at 1000 V AC 50/60 Hz (AC-3e)90 kW at 230 V AC 50/60 Hz (AC-3)160 kW at 400 V AC 50/60 Hz (AC-3)160 kW at 415 V AC 50/60 Hz (AC-3)200 kW at 440 V AC 50/60 Hz (AC-3)200 kW at 500 V AC 50/60 Hz (AC-3)220 kW at 690 V AC 50/60 Hz (AC-3)185 kW at 1000 V AC 50/60 Hz (AC-3)90 kW at 230 V AC 50/60 Hz (AC-4)160 kW at 400 V AC 50/60 Hz (AC-4)160 kW at 415 V AC 50/60 Hz (AC-4)185 kW at 440 V AC 50/60 Hz (AC-4)200 kW at 500 V AC 50/60 Hz (AC-4)220 kW at 690 V AC 50/60 Hz (AC-4)185 kW at 1000 V AC 50/60 Hz (AC-4)
Net weight8.2 kg
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529IP2X front face with shrouds conforming to VDE 0106
hold-in power consumption in W (DC)9.0 W
RangeTeSys
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
[Uimp] rated impulse withstand voltage8 kV
Mounting supportPlate
Connection pitch45 mm
[Ui] rated insulation voltage1000 V
Obtain a Quote for Schneider AC-3 440V High Power Contactor LC1G330LSEA at economical prices. Specifications Overview for LC1G330LSEA reveals device short name LC1G, designed for efficient power management in industrial applications. The sensor has a power dissipation per pole of 30 W AC-1 - Ith 440 A16 W AC-3 - Ith 330 A, ensuring energy-efficient operation. It operates within a broad ambient temperature range of -25…60 °C, making it suitable for various environmental conditions. The rated operational voltage [Ue] is up to <= 1000 V AC 50/60 Hz<= 460 V DC, providing robust power handling. Its rated breaking capacity reaches 2940 A at 440 V, ensuring reliable performance during switching. The auxiliary contact composition includes 1 NO + 1 NC, enhancing flexibility in control applications. With the mechanical durability of 8 Mcycles, the sensor guarantees long-lasting reliability. Operating times include a closing time of 40...70 ms closing15...50 ms opening quick and responsive operation. Take the First Step with a Quote for your requirement of Schneider AC-3 440V High Power Contactor. Our commitment to better pricing and exceptional support sets us apart from other Competitors.