Maximum number of function block definitions: 128 Maximum number of instances: 256; Languages usable in function block definitions: Ladder diagrams, structured text (ST)
Instruction length
1 to 7 steps per instruction
Instructions
Approx. 500 (function codes: 3 digits)
Instruction execution time
Basic instructions: 0.55 μs min. Special instructions: 4.1 μs min
Common processing time
0.4ms
Operating voltage range
85 to 264 VAC
Power consumption
50 VA max.
Inrush current
100 to 120 VAC inputs:
20 A max. (for cold start at room temperature)
8 ms max.
200 to 240 VAC inputs:
40 A max. (for cold start at room temperature), 8 ms max.
External power supply
300 mA at 24 VDC
Insulation resistance
20 MΩ min. (at 500 VDC) between the external AC terminals
and GR terminals
Dielectric strength
2,300 VAC at 50/60 Hz for 1 min between the external AC and
GR terminals, leakage current: 5 mA max.
Noise immunity
Conforms to IEC 61000-4-4. 2 kV (power supply line)
Vibration resistance
Conforms to JIS C60068-2-6. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for
80 minutes each. Sweep time: 8 minutes × 10 sweeps = total time of 80 minutes)
Shock resistance
Conforms to JIS C60068-2-27. 147 m/s2 three times each in X, Y, and Z directions
Ambient operating temperature
0 to 55°C
Ambient humidity
10% to 90% (with no condensation)
Ambient operating environment
No corrosive gas
Ambient storage temperature
−20 to 75°C (Excluding battery.)
Power holding time
10 ms min.
Mail Us for your needs in Omron Logical PLC 24 Inputs CP1L-M40DT-A with budget-friendly prices. The Main Technical Parameters of CP1L-M40DT-A include 100 to 240 VAC 50/60 Hz power supply and Transistor output (sinking). It has 24 inputs and 16 outputs, utilizing a Stored program method and Cyclic scan with immediate refreshing for control. Programming is done through a Ladder diagram with Maximum number of function block definitions: 128 Maximum number of instances: 256; Languages usable in function block definitions: Ladder diagrams, structured text (ST). The instruction length ranges 1 to 7 steps per instruction, with Approx. 500 (function codes: 3 digits) instructions available. It operates within a voltage range of 85 to 264 VAC and consumes 50 VA max. . Customize Your Experience with a Quote for your requirement of Omron Logical PLC 24 Inputs. Experience the difference with our competitive pricing and superior support over other Suppliers.Mail Us for your needs in Omron Logical PLC 24 Inputs CP1L-M40DT-A with budget-friendly prices. The Main Technical Parameters of CP1L-M40DT-A include 100 to 240 VAC 50/60 Hz power supply and Transistor output (sinking). It has 24 inputs and 16 outputs, utilizing a Stored program method and Cyclic scan with immediate refreshing for control. Programming is done through a Ladder diagram with Maximum number of function block definitions: 128 Maximum number of instances: 256; Languages usable in function block definitions: Ladder diagrams, structured text (ST). The instruction length ranges 1 to 7 steps per instruction, with Approx. 500 (function codes: 3 digits) instructions available. It operates within a voltage range of 85 to 264 VAC and consumes 50 VA max. . Customize Your Experience with a Quote for your requirement of Omron Logical PLC 24 Inputs. Experience the difference with our competitive pricing and superior support over other Suppliers.