Technical specifications of Omron PLC with 60 Points Digital Input/Output CP2E-N60DT-A:

SpecValue
Inputs36 points
Outputs24 points
Output typeTransistor (sinking)
Program capacity10K steps (FB capacity: 10K steps)
Supply voltage100 to 240 VAC 50/60 Hz

Omron PLC with 60 Points Digital Input/Output CP2E-N60DT-A Technical Specifications:

SpecificationValue
Number of pointsCPU Units with 60 points
Inputs36 points
Outputs24 points
Output typeTransistor (sinking)
Program capacity10K steps (FB capacity: 10K steps)
Data memory capacity16K words
Current consumption 5 VDC0.71 A
Current consumption 24 VDC0.03 A
Dimensions (H × D × W)90mm *1 × 80mm *2 × 195mm
Supply voltage100 to 240 VAC 50/60 Hz
Operating voltage range85 to 264 VAC
Power consumption50 VA/100 VAC max., 70 VA/240 VAC max.
Inrush current120 VAC, 20 A for 8 ms max. for cold start at room temperature, 240 VAC, 40 A for 8 ms max. for cold start at room temperature
Insulation resistance20 MΩ min. (at 500 VDC) between the external AC, terminals and GR terminals
Power interrupt time10 ms min.
Altitude2,000 m max
AtmosphereNo corrosive gas
Ambient humidity10% to 90%
Ambient operating temperature20 to 60°C
Ambient storage temperature-20 to 75°C (excluding battery)
Weight780g max.
Reach Us by Email for Omron PLC with 60 Points Digital Input/Output CP2E-N60DT-A at Discounted Rates. Key Technical Features of CP2E-N60DT-A includes CPU Units with 60 points,36 points inputs and 24 points Transistor (sinking) outputs. It features a program capacity of 10K steps (FB capacity: 10K steps) and a data memory capacity of 16K words. The PLC operates at 100 to 240 VAC 50/60 Hz with an operating voltage range of 85 to 264 VAC and a power consumption of 50 VA/100 VAC max., 70 VA/240 VAC max.. Its current consumption is 0.71 A at 5 VDC and 0.03 A at 24 VDC. The dimensions are 90mm *1 × 80mm *2 × 195mm. It has an insulation resistance of 20 MΩ min. (at 500 VDC) between the external AC, terminals and GR terminals, and can handle power interruptions of 10 ms min.. at altitudes up to 2,000 m max with No corrosive gas. Navigate Your Needs with a Quote for your requirement of Omron PLC with 60 Points Digital Input/Output. Our pricing and support are unrivaled, especially when compared to other Competitors.