H3CA-8 DC110: Omron Flush Mounting Timer
Technical Specifications of Omron Flush Mounting Timer H3CA-8 DC110:
Spec | Value |
---|---|
Rated Supply Voltage | 110 VDC (Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier)) |
Time ranges(Number of ranges) | 7 |
Input Method | No-voltage input (open and short-circuit) |
Output Mode | A: Power ON delay |
Omron Flush Mounting Timer H3CA-8 DC110 Technical Specifications:
Specification | Value |
---|---|
Rated supply voltage | 110 VDC (Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier)) |
Operating voltage range | 85 to 110% of rated supply voltage |
Power consumption | Approx. 1 W |
Time ranges(Number of ranges) | 7 |
Input method | No-voltage input (open and short-circuit) |
Output modes | A: Power ON delay |
Control output (Contact output) | Time-limit contact: DPDT Resistive load: 3 A at 250 VAC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value) |
Reset system | Self-reset |
Power reset | Reset time: 0.1 s max. |
Display method | LCD 3 digit |
Ambient temperature (Operating) | -10 to 55 ℃ (with no icing) |
Ambient humidity (Operating) | 35 to 85% |
Accuracy of operating time | ±0.3% ±0.05 s (The values are based on the set value.) |
Setting error | ±0.5% ±0.05 s (The values are based on the set value.) |
Influence of voltage | ±0.3% ±0.05 s (The values are based on the set value.) |
Influence of temperature | ±0.3% ±0.05 s (The values are based on the set value.) |
100 MΩ min. (at 500 VDC) | Insulation resistance |
Time ranges | 0.1 to 99.9 s 1 to 999 s 0.1 to 99.9 min 1 to 999 min 0.1 to 99.9 h 1 to 999 h 10 to 9990 h |
Dielectric strength | Between current carrying metal parts and non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1000 VAC 50/60 Hz 1 min |
Impulse withstand voltage | Between power terminals: 3 kV Between current carrying terminals and exposed non-current carrying metal parts: 4.5 kV |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 1 hour Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
Shock resistance | Destruction: 1,000 m/s2, 3 times each in 6 directions Malfunction: 100 m/s2, 3 times each in 6 directions |
Life expectancy (relay output) | Electrical: 100,000 operations min. (3 A at 250 VAC resistive load at 1800 operations/h) Mechanical: 10 million operations min. (under no load at 1,800 operations/h) |
Degree of protection | IP40 |
Mounting method | Flush mounting / Surface mounting |
External connection method | 8-pin round socket |
Applicable socket | P2CF-08, P2CF-08-E, P3G-08, PL08 |
Accessory (sold separately) | Soft Cover: Y92A-48D Hard Cover: Y92A-48B Flush mounting adapter: Y92F-30/Y92F-70/Y92F-71 |
Mail Us for your needs in , H3CA-8 DC110 with budget-friendly prices. The Main Technical Parameters of H3CA-8 DC110 include 110 VDC (Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier)), 85 to 110% of rated supply voltage, Approx. 1 W, 7. Additionally, it provides Self-reset, Time-limit contact: DPDT
Resistive load: 3 A at 250 VAC
Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value), No-voltage input (open and short-circuit). Customize Your Experience with a Quote for your requirement of Omron Flush Mounting Timer. Experience the difference with our competitive pricing and superior support over other Suppliers.