H3CA-FA | Omron Front Screw Terminal Timer | IndMALL
+91 79955 44066 sales@indmall.in

H3CA-FA: Omron Front Screw Terminal Timer

Technical Specifications of Omron Front Screw Terminal Timer H3CA-FA:

SpecValue
Rated Supply Voltage24 to 240 VAC (50/60 Hz) 12 to 240 VDC (Ripple 20% max. (Single-phase full-wave rectified power sources may be used for 24 to 240 VDC.))
Time ranges(Number of ranges)7
Input MethodNo-voltage input (open and short-circuit)
Output ModeA: ON delay B: Repeat cycle C: Signal ON/OFF delay D: Signal OFF delay E: Interval F: One shot and flicker G: Signal ON/OFF delay H: Signal OFF delay

Omron Front Screw Terminal Timer H3CA-FA Technical Specifications:

SpecificationValue
Rated supply voltage24 to 240 VAC (50/60 Hz) 12 to 240 VDC (Ripple 20% max. (Single-phase full-wave rectified power sources may be used for 24 to 240 VDC.))
Operating voltage range90 to 110% of rated supply voltage (21.6 to 264 VAC/10.8 to 264 VDC)
Power consumptionApprox. 0.2 to 4 VA/Approx. 0.2 to 2 W
Time ranges(Number of ranges)7
Input methodNo-voltage input (open and short-circuit)
Output modesA: ON delay B: Repeat cycle C: Signal ON/OFF delay D: Signal OFF delay E: Interval F: One shot and flicker G: Signal ON/OFF delay H: Signal OFF delay
Control output (Contact output)Time-limit contact: DPDT Resistive load: 3 A at 250 VAC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
Reset systemSelf-reset/External reset
Power resetReset time: 0.5 s max.
Display methodLCD 3 digit
Ambient temperature (Operating)-10 to 55 ℃ (with no icing)
Ambient humidity (Operating)35 to 85%
Accuracy of operating time±0.3% ±0.05 s (The values are based on the set value.)
Setting error±0.5% ±0.05 s (The values are based on the set value.)
Influence of voltage±0.3% ±0.05 s (The values are based on the set value.)
Influence of temperature±0.3% ±0.05 s (The values are based on the set value.)
100 MΩ min. (at 500 VDC)Insulation resistance
Time ranges0.1 to 99.9 s 1 to 999 s 0.1 to 99.9 min 1 to 999 min 0.1 to 99.9 h 1 to 999 h 10 to 9990 h
Dielectric strengthBetween current carrying metal parts and non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 5 kV Between current carrying terminals and exposed non-current carrying metal parts: 5 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 1 hour Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 1,000 m/s2, 3 times each in 6 directions Malfunction: 100 m/s2, 3 times each in 6 directions
Life expectancy (relay output)Electrical: 100,000 operations min. (3 A at 250 VAC resistive load at 1800 operations/h) Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Degree of protectionIP40
Mounting methodSurface mounting
External connection methodFront screw terminals
Applicable socket-
Accessory (sold separately)-
Mail Us for your needs in Omron Front Screw Terminal Timer, H3CA-FA with budget-friendly prices. The Main Technical Parameters of H3CA-FA include 24 to 240 VAC (50/60 Hz) 12 to 240 VDC (Ripple 20% max. (Single-phase full-wave rectified power sources may be used for 24 to 240 VDC.)), 90 to 110% of rated supply voltage (21.6 to 264 VAC/10.8 to 264 VDC), Approx. 0.2 to 4 VA/Approx. 0.2 to 2 W, 7. Additionally, it provides Self-reset/External reset, Time-limit contact: DPDT Resistive load: 3 A at 250 VAC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value), No-voltage input (open and short-circuit). Customize Your Experience with a Quote for your requirement of Omron Front Screw Terminal Timer. Experience the difference with our competitive pricing and superior support over other Suppliers.