Technical Specifications of Omron 100-120V Flicker OFF Timer H3CR-G8EL AC100-120:

SpecValue
Rated power supply voltage100/110/120 VAC 50/60 Hz
Allowable voltage variable range85 to 110% of the power supply voltage
Power consumptionApprox. 6 VA (at 120 VAC) Approx. 2.6 W (at 120 VAC)
Operation start voltage10% max. of rated supply voltage

Omron 100-120V Flicker OFF Timer H3CR-G8EL AC100-120 Technical Specifications:

SpecificationValue
Rated power supply voltage100/110/120 VAC 50/60 Hz
Allowable voltage variable range85 to 110% of the power supply voltage
Power ConsumptionApprox. 6 VA (at 120 VAC) Approx. 2.6 W (at 120 VAC)
Operation Start Voltage10% max. of rated supply voltage
Input Signals-
Input Method-
No Voltage Input-
Number of Times Ranges4
Opeation ModeStar-delta
Control Output TypeTime-limit: SPST-NO (Start operation circuit) SPST-NO (Delta operation circuit) ,Instantaneous: SPST-NO
Control output (Contact output)Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
Operating resettingTime-limit operation/Self-reset
Ambient temperature rangeOperating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing)
Ambient humidity rangeOperating: 35 to 85%
Accuracy of operating time±0.2% FS max
Setting error±5% FS ±50 ms max.
Influence of voltage±0.2% FS max.
Influence of temperature±1% FS max
Insulation resistance100 MΩ min. (at 500 VDC)
Dielectric strengthBetween current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 5 kV Between current carrying terminals and exposed non-current carrying metal parts: 5 kV
Noise immunity±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunityMulfunction: 8 kV, Destruction: 15 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 980 m/s2, 3 times each in 6 directions Malfunction: 294 m/s2, 3 times each in 6 directions
Life expectancy (relay output)Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h) Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Degree of protectionIP40 (panel surface)
Connecting method8-pin round socket
WeightApprox. 130 g
Please speak to our Technical Engineer for Omron 100-120V Flicker OFF Timer, H3CR-G8EL AC100-120 at attractive prices. Technical Specs Summary of H3CR-G8EL AC100-120 includes 100/110/120 VAC 50/60 Hz, 85 to 110% of the power supply voltage, Star-delta, Time-limit: SPST-NO (Start operation circuit) SPST-NO (Delta operation circuit) ,Instantaneous: SPST-NO. And Special Features Are Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value), Time-limit operation/Self-reset, Approx. 130 g. Match Your Needs with a Quote for your requirement of Omron 100-120V Flicker OFF Timer. We lead with pricing that's more favorable and support that's more attentive than other Suppliers & Traders.