H3CR-H8L AC/DC24 S: Omron 24V Solid-state Timer
Technical Specifications of Omron 24V Solid-state Timer H3CR-H8L AC/DC24 S:
Spec | Value |
---|---|
Rated power supply voltage | 24 VAC 50/60 Hz 24 VDC Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier) |
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Power consumption | Approx. 0.17 VA (at 24 VAC) Approx. 0.15 W (at 24 VAC)/Approx. 1 W (at 24 VDC) |
Operation start voltage | 30% max. of rated supply voltage |
Omron 24V Solid-state Timer H3CR-H8L AC/DC24 S Technical Specifications:
Specification | Value |
---|---|
Rated power supply voltage | 24 VAC 50/60 Hz 24 VDC Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier) |
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Power Consumption | Approx. 0.17 VA (at 24 VAC) Approx. 0.15 W (at 24 VAC)/Approx. 1 W (at 24 VDC) |
Operation Start Voltage | 30% max. of rated supply voltage |
Input Signals | - |
Input Method | - |
No Voltage Input | - |
Number of Times Ranges | 4 |
Opeation Mode | Power OFF-delay |
Control Output Type | Time-limit: DPDT |
Control output (Contact output) | Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value) |
Operating resetting | Instantaneous operation/Time-limit reset |
Ambient temperature range | Operating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing) |
Ambient humidity range | Operating: 35 to 85% |
Accuracy of operating time | ±0.2% FS max. (±0.2% ±10 ms in a range of 0.6 s and 1.2 s) |
Setting error | ±5% FS ±50 ms max. |
Influence of voltage | ±0.2% FS max. (±0.2% ±10 ms in a range of 0.6 s and 1.2 s) |
Influence of temperature | ±1% FS max. (±1% ±10 ms in a range of 0.6 s and 1.2 s) |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength | Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min |
Impulse withstand voltage | Between power terminals: 1 kV Between current carrying terminals and exposed non-current carrying metal parts: 1.5 kV |
Noise immunity | ±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) |
Static immunity | Mulfunction: 8 kV, Destruction: 15 kV |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
Shock resistance | Destruction: 980 m/s2, 3 times each in 6 directions Malfunction: 98 m/s2, 3 times each in 6 directions |
Life expectancy (relay output) | Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1200 operations/h) Mechanical: 10 million operations min. (under no load at 1,200 operations/h) |
Degree of protection | IP40 (panel surface) |
Connecting method | 8-pin round socket |
Weight | Approx. 120 g |
Mail Us for your needs in Omron 24V Solid-state Timer, H3CR-H8L AC/DC24 S with budget-friendly prices. The Main Technical Parameters of H3CR-H8L AC/DC24 S include 24 VAC 50/60 Hz
24 VDC Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier), 85 to 110% of the power supply voltage, Approx. 0.17 VA (at 24 VAC)
Approx. 0.15 W (at 24 VAC)/Approx. 1 W (at 24 VDC), 30% max. of rated supply voltage. Additionally, it provides Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC
Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value), Time-limit: DPDT, 4. Customize Your Experience with a Quote for your requirement of Omron 24V Solid-state Timer. Experience the difference with our competitive pricing and superior support over other Suppliers.