H3DK-GA DC12 | Omron DIN Mount Timer | IndMALL Automation
+91 79955 44066 sales@indmall.in

H3DK-GA DC12: Omron DIN Mount Timer

Technical Specifications of Omron DIN Mount Timer H3DK-GA DC12:

SpecValue
Rated power supply voltage12 VDC Ripple 20% max.
Allowable voltage variable range90 to 110% of the power supply voltage
Voltage Input-
Reset voltage10% max. of rated supply voltage

Omron DIN Mount Timer H3DK-GA DC12 Technical Specifications:

SpecificationValue
Rated power supply voltage12 VDC Ripple 20% max.
Allowable voltage variable range90 to 110% of the power supply voltage
Operating resettingTime-limit operation/Self-reset
Input method-
Star-delta transfer timeselectable from 0.05 s, 0.1 s, 0.25 s and 0.5 s
Voltage input-
Power consumptionApprox. 0.9 W (at 12 VDC)
Reset voltage10% max. of rated supply voltage
Number of time ranges2
Operation modeStar-delta
Control output (Type)Time-limit: SPDT
Control output (Contact output)Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC/0.5 A max. at 125 VDC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
Ambient temperature rangeOperating: -20 to 55 ℃ (with no icing) Storage: -40 to 70 ℃ (with no icing)
Ambient humidity rangeOperating: 25 to 85%
Accuracy of operating time±1% FS max. (±1% ±10 ms in a range of 1.2 s)
Setting error±10% FS ±0.05 s max.
Influence of voltage±0.5% FS max. (±0.5% ±10 ms in a range of 1.2 s)
Influence of temperature±2% FS max. (±2% ±10 ms in a range of 1.2 s)
Insulation resistance100 MΩ min. (at 500 VDC)
Dielectric strengthBetween current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltageBetween power terminals: 1 kV Between current carrying terminals and exposed non-current carrying metal parts: 1.5 kV
Noise immunity±1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunityMulfunction: 4 kV, Destruction: 8 kV
Vibration resistanceDestruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistanceDestruction: 1,000 m/s2, 3 times each in 6 directions Malfunction: 100 m/s2, 3 times each in 6 directions
Life expectancy (relay output)Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Degree of protectionIP30 (Terminal Block: IP20)
Connecting methodTerminal blocks
AccessoriesUser label
WeightApprox. 120 g
Please speak to our Technical Engineer for Omron DIN Mount Timer, H3DK-GA DC12 at attractive prices. Technical Specs Summary of H3DK-GA DC12 includes 12 VDC Ripple 20% max., 90 to 110% of the power supply voltage, Approx. 0.9 W (at 12 VDC), 10% max. of rated supply voltage. And Special Features Are 2, Star-delta, Terminal blocks. Match Your Needs with a Quote for your requirement of Omron DIN Mount Timer. We lead with pricing that's more favorable and support that's more attentive than other Suppliers & Traders.