H3DK-HCS AC100-120V: Omron Relay Output Terminal Block Timer
Technical Specifications of Omron Relay Output Terminal Block Timer H3DK-HCS AC100-120V:
Spec | Value |
---|---|
Rated power supply voltage | 100 to 120 VAC 50/60 Hz |
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Voltage Input | - |
Reset voltage | 10% max. of rated supply voltage |
Omron Relay Output Terminal Block Timer H3DK-HCS AC100-120V Technical Specifications:
Specification | Value |
---|---|
Rated power supply voltage | 100 to 120 VAC 50/60 Hz |
Allowable voltage variable range | 85 to 110% of the power supply voltage |
Operating resetting | Instantaneous operation/Time-limit reset |
Input method | - |
Star-delta transfer time | - |
Voltage input | - |
Power consumption | Approx. 11.7 VA (at 120 VAC) |
Reset voltage | 10% max. of rated supply voltage |
Number of time ranges | 2 |
Operation mode | Power OFF-delay |
Control output (Type) | Relay output (SPDT) |
Control output (Contact output) | Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC/0.5 A max. at 125 VDC Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value) |
Ambient temperature range | Operating: -20 to 55 ℃ (with no icing) Storage: -40 to 70 ℃ (with no icing) |
Ambient humidity range | Operating: 25 to 85% |
Accuracy of operating time | ±1% FS max. (±1% ±10 ms in a range of 1.2 s) |
Setting error | ±10% FS ±0.05 s max. |
Influence of voltage | ±0.5% FS max. (±0.5% ±10 ms in a range of 1.2 s) |
Influence of temperature | ±2% FS max. (±2% ±10 ms in a range of 1.2 s) |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength | Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min |
Impulse withstand voltage | Between power terminals: 5 kV Between current carrying terminals and exposed non-current carrying metal parts: 5 kV |
Noise immunity | ±1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) |
Static immunity | Mulfunction: 4 kV, Destruction: 8 kV |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
Shock resistance | Destruction: 1,000 m/s2, 3 times each in 6 directions Malfunction: 100 m/s2, 3 times each in 6 directions |
Life expectancy (relay output) | Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) Mechanical: 10 million operations min. (under no load at 1,800 operations/h) |
Degree of protection | IP30 (Terminal Block: IP20) |
Connecting method | Terminal blocks |
Accessories | User label |
Weight | Approx. 120 g |
Get A Quote for Omron Relay Output Terminal Block Timer, H3DK-HCS AC100-120V at the best price. Here are the brief Technical Specifications of H3DK-HCS AC100-120V: Approx. 11.7 VA (at 120 VAC), 85 to 110% of the power supply voltage, 100 to 120 VAC 50/60 Hz, Omron Relay Output Terminal Block Timer H3DK-HCS AC100-120V Technical Specifications:. And it offers Power OFF-delay, 2, 10% max. of rated supply voltage. It's Time to get a Quote for your requirement of Omron Relay Output Terminal Block Timer. We guarantee unmatched pricing and unparalleled support compared to other Distributors.