H7HP-C8D: Omron 8 Digits Total Counter
Technical Specifications of Omron 8 Digits Total Counter H7HP-C8D:
Spec | Value |
---|---|
Function | Total Counter |
Rated Supply Voltage | 12 to 24 VDC (Ripple 20 % max.) |
Count Range | -99999 to 999999 |
Max Counting Speed | 30 Hz/5 kHz (switching) |
Omron 8 Digits Total Counter H7HP-C8D Technical Specifications:
Specification | Value |
---|---|
Function | Total Counter |
Rated Supply Voltage | 12 to 24 VDC (Ripple 20 % max.) |
Operating Voltage Range | 85 to 110% of the power supply voltage |
Power Consumption | 0.6 W max. |
External Power Supply | - |
Count range | -99999 to 999999 |
Max Counting Speed | 30 Hz/5 kHz (switching) |
Counter Input Mode | Increment/decrement (UP/DOWN (individual input)) |
Reset System | External and manual reset |
Time Counter Ranges | - |
Counter Time Ranges | - |
Time counter Set value read selector | - |
Time counter Reset system | - |
Input signal | Count 1/start, Count 2/gate, Reset, Key protect |
Input method | No-voltage (NPN, contact input)/Voltage input (PNP) selectable |
No-voltage input (No-contact input) | Short-circuit (ON) impedance: 1 kΩ max. Residual voltage: 2 V max.DC Open circuit impedance: 100 kΩ min. |
No-voltage input (Contact input) | Short-circuit (ON) impedance: 1 kΩ max. Short-circuit (ON) residual voltage: 2 VDC max. Open circuit impedance: 100 kΩ min. |
Voltage input | Hight level: 9 to 24 VDC (ON voltage) Low level: 5 VDC max. (OFF voltage) Short-circuit (ON) impedance: 1 kΩ max. Open circuit impedance: 100 kΩ min. |
Display method | 7-segment backlit negative transmissive Red LCD |
Display Digits | 8 digit |
Memory backup methods Ambient humidity (Operating) Insulation resistance | Method: EEP-ROM, Number of rewite: 200,000 operations min., Store data: 20 years min. |
Ambient temperature (Storage) | -10 to 55 ℃ (with no icing) |
Ambient temperature (Operating) | -25 to 65 ℃ (with no icing) |
Ambient humidity (Operating) | 35 to 85 % |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric withstand voltage | Between current carrying terminals and exposed non-current carrying metal parts: 2000 VAC 50/60 Hz 1 min Between power terminals and control input terminals: 2000 VAC 50/60 Hz 1 min |
Impulse withstand voltage | Between power terminals: 3.0 kV Between current carrying terminals and exposed non-current carrying metal parts: 4.5 kV |
Noise immunity | Between power terminals: ±1.5 kV Between input terminals: ±480 V square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) |
Static immunity | Display: Mulfunction: 8 kV, Destruction: 15 kV Dip switch: Mulfunction: 4 kV, Destruction: 8 kV |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
Shock resistance | Destruction: 294 m/s2, 3 times each in 3 axes each directions Malfunction: 196 m/s2, 3 times each in 3 axes each directions |
Degree of protection | Case front: IP66 Oil-resistant type and NEMA Type 4 (indoors) |
External connection method | Screw terminal |
Case color | Gray smoke (Front: Light gray (Munsell 5Y7/1)) |
Weight | Approx. 115 g |
Give Us a Call for Omron 8 Digits Total Counter, H7HP-C8D at the lowest pricing. In-depth Technical Analysis of H7HP-C8D includes 12 to 24 VDC (Ripple 20 % max.), -99999 to 999999, 30 Hz/5 kHz (switching), 0.6 W max.. It functionality Includes 85 to 110% of the power supply voltage, -, Total Counter. Elevate Your Project with a Quote for your requirement of Omron 8 Digits Total Counter. Our promise: More affordable pricing and more personalized support than other Distributors & Dealers.