KCD2-SON-Ex1-R3 - P&F 14 mA Rated Current Switch Amplifier
+91 79955 44066 sales@indmall.in

KCD2-SON-Ex1-R3: - P&F 14 mA Rated Current Switch Amplifier

Technical Specifications of P&F 14 mA Rated Current Switch Amplifier KCD2-SON-Ex1-R3:

SpecValue
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch)
Supply ConnectionPower Rail or terminals 9+, 10-
Outputsignal or fault message, passive transistor output (resistive), 0-signal: 19 kΩ ±5 %, 1-signal: 100 Ω ... 600 Ω, fault: > 100 kΩ
Connectionscrew terminals

P&F 14 mA Rated Current Switch Amplifier KCD2-SON-Ex1-R3, Technical Specifications:

SpecificationValue
Signal typeDigital Input
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Rated current18 ... 14 mA
Power dissipation≤ 500 mW
Power consumption-
Connection side (Input)field side
Ripple≤ 10 %
Connection (Input)terminals 1+, 2-
Open circuit voltage/short-circuit current (Input)approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis (Input)1.2 ... 2.1 mA / approx. 0.2 mA
Connection side (Output)control side
Connection (Output)output I: terminals 5, 6 ; output II: terminals 7, 8
Response time≤ 200 µs
Signal level-
Output Isignal or fault message, passive transistor output (resistive), 0-signal: 19 kΩ ±5 %, 1-signal: 100 Ω ... 600 Ω, fault: > 100 kΩ
Output IIsignal or fault message, passive transistor output (resistive), 0-signal: 19 kΩ ±5 %, 1-signal: 100 Ω ... 600 Ω, fault: > 100 kΩ
Minimum switch current-
Switching frequency≤ 5 kHz
Display elementsLEDs
Control elementsDIP switch
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch)
Connectionscrew terminals
Mountingon 35 mm DIN mounting rail
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Degree of protectionIP20
Send Your Inquiry for P&F 14 mA Rated Current Switch Amplifier KCD2-SON-Ex1-R3 with cost-effective solutions. Essential Technical Specs of KCD2-SON-Ex1-R3, are Digital Input signal type, Power Rail or terminals 9+, 10- supply connection, Digital Input rated voltage, 18 ... 14 mA rated curent, field side input connection, ≤ 200 µs, response time, control side, output connection, signal or fault message, passive transistor output (resistive), 0-signal: 19 kΩ ±5 %, 1-signal: 100 Ω ... 600 Ω, fault: > 100 kΩ output, ≤ 5 kHz switching frequency, with dimensions of 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) screw terminals connection, on 35 mm DIN mounting rail mounting, -20 ... 60 °C (-4 ... 140 °F) ambient temperature IP20 degree of protection. Capture the Best Deal with a Quote for your requirement of P&F 14 mA Rated Current Switch Amplifier. Our pricing and support are designed to exceed the standards of other Traders & Suppliers.