Phoenix PS-EE-2G/1AC/24DC/75W/SC (1234301) | Reach Out Today
+91 79955 44066 sales@indmall.in

PS-EE-2G/1AC/24DC/75W/SC: 1234301 - Phoenix Single Phase Essential Power Supply

Technical Specifications of Phoenix Single Phase Essential Power Supply PS-EE-2G/1AC/24DC/75W/SC 1234301:

SpecValue
Efficiencytyp. 88 % (120 V AC)
Nominal output voltage24 V DC
Nominal output current (IN)max. 3.125 A (PN = 75 W)
MountingDIN rail mounting

Phoenix Single Phase Essential Power Supply PS-EE-2G/1AC/24DC/75W/SC, 1234301 Technical Specifications:

SpecificationValue
Nominal input voltage range100 V AC ... 240 V AC
Input voltage range110 V AC ... 240 V AC ±10 % (PN = 75 W)
Inrush currenttyp. 27 A (at 25 °C)
Frequency range (fN)50 Hz ... 60 Hz ±10 %
Efficiencytyp. 88 % (120 V AC)
Nominal output voltage24 V DC
Nominal output current (IN)max. 3.125 A (PN = 75 W)
Short-circuit-proofyes
Protection against overvoltage at the output (OVP)≤ 35 V DC
Residual rippletyp. 50 mVPP (with nominal values)
Power loss nominal load max.< 9 W (230 V AC)
Insulation voltage input/output4 kV AC (type test)
Mounting typeDIN rail mounting
Degree of protectionIP20
Ambient temperature (operation)-20 °C ... 70 °C (Derating >45°C: 2.5%/K)
EMC requirements for noise immunityEN 61000-6-2
EMC requirements for noise emission
Mail Us for your needs in Phoenix Single Phase Essential Power Supply PS-EE-2G/1AC/24DC/75W/SC part no: 1234301 with budget-friendly prices. The Main Technical Parameters of PS-EE-2G/1AC/24DC/75W/SC, 1234301 inludce 100 V AC ... 240 V AC operates with a nominal input voltage range, ensuring versatility across various power systems. With an impressive efficiency of approximately typ. 88 % (120 V AC) it guarantees optimal energy use. The sensor provides a nominal output voltage of 24 V DC and supports a maximum output current of max. 3.125 A (PN = 75 W) making it suitable for demanding tasks. The residual ripple is typ. 50 mVPP (with nominal values) ensuring stable and reliable performance. Designed for easy installation, the sensor features DIN rail mounting and is rated with a IP20 degree of protection. It operates effectively in ambient temperatures ranging from -20 °C ... 70 °C (Derating >45°C: 2.5%/K). Customize Your Experience with a Quote for your requirement of Phoenix Single Phase Essential Power Supply. Experience the difference with our competitive pricing and superior support over other Suppliers.