REL-IR-BL/L-125DC/4X21: 1109561 - Phoenix Input Voltage 125V DC Single Relay
Technical Specifications of Phoenix Input Voltage 125V DC Single Relay REL-IR-BL/L-125DC/4X21 1109561:
Spec | Value |
---|---|
Product Type | Single relay |
Mechanical service life | 3x 107 cycles |
Nominal input voltage UN | 125 V DC |
Input voltage range | 100 V DC ... 243.8 V DC (20 °C) |
Phoenix Input Voltage 125V DC Single Relay REL-IR-BL/L-125DC/4X21, 1109561 Technical Specifications:
Specification | Value |
---|---|
Product type | Single relay |
Mechanical service life | 3x 107 cycles |
Insulation | Basic insulation |
Overvoltage category | III |
Pollution degree | 2 |
Service life electrical | see diagram |
Maximum power dissipation for nominal condition | 0.88 W |
Test voltage (Winding/contact) | 2.5 kVrms (50 Hz, 1 min., winding/contact) |
Test voltage (Changeover contact/changeover contact) | 2 kVrms (50 Hz, 1 min., changeover contact/changeover contact) |
Rated insulation voltage | 250 V AC |
Rated surge voltage | 5 kV |
Nominal input voltage UN | 125 V DC |
Input voltage range | 100 V DC ... 243.8 V DC (20 °C) |
Drive and function | monostable |
Drive (polarity) | polarized |
Typical input current at UN | 6.1 mA |
Typical response time | 10 ms |
Coil voltage | 125 V DC |
Status display | LED (yellow) |
Contact switching type | 4 changeover contacts |
Type of switch contact | Single contact |
Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 12 V (10 mA) |
Limiting continuous current | 6 A |
Maximum inrush current | 12 A (20 ms, N/O contacts) |
Min. switching current | 10 mA (12 V) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC) |
Connection method | Plug-in connection |
Width | 22.5 mm |
Height | 28 mm |
Depth | 35.5 mm |
Degree of protection | RT II |
Degree of protection (Installation location) | ≥ IP54 (Installation location) |
Ambient temperature (operation) | -40 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Standards/regulations | EN 61810-1 |
Mounting type | Plug-in mounting |
Mounting position | any |
Mains frequency | - |
Typical release time range | - |
Coil resistance | 20.8 kΩ ±15 % |
Switching capacity | - |
Motor load according to UL 508 | - |
Input power dissipation for UN | - |
3-phase motor load | - |
Product family | - |
Relay type | - |
Test voltage () | - |
Degree of protection (Relay) | - |
Inrush current, minimum | - |
Non-operate voltage | - |
Safe operate voltage | - |
Test voltage (N/O contact / N/O contact) | - |
Reach Us by Email for Phoenix Input Voltage 125V DC Single Relay REL-IR-BL/L-125DC/4X21 part no: 1109561 at Discounted Rates. Key Technical Features of REL-IR-BL/L-125DC/4X21, 1109561 are mechanical service life of 3x 107 cycles, designed for demanding industrial applications. The sensor operates at a nominal input voltage of 125 V DC, with an input voltage range of 100 V DC ... 243.8 V DC (20 °C). The typical input current at UN is 6.1 mA with a response time of 15 ms. The sensor supports a maximum switching voltage of 250 V AC/DC, and a minimum switching voltage of 12 V (10 mA). It has a limiting continuous current of 6 A, with a maximum inrush current of 12 A (20 ms, N/O contacts), and a minimum switching current of 10 mA (12 V). The interrupting rating for ohmic loads is 144 W (24 V DC). The connection method is via a Plug-in connection, with a degree of protection rated at RT II. The sensor operates reliably in ambient temperatures ranging from -40 °C ... 70 °C. Navigate Your Needs with a Quote for your requirement of Phoenix Input Voltage 125V DC Single Relay. Our pricing and support are unrivaled, especially when compared to other Competitors.