Phoenix REL-IR4/DP-220DC/4X21 (2905728) | Contact Us Today
+91 79955 44066 sales@indmall.in

REL-IR4/DP-220DC/4X21: 2905728 - Phoenix 4 PDT Contacts Single Relay

Phoenix Contact REL-IR4/DP-220DC/4X21 2905728

Technical Specifications of Phoenix 4 PDT Contacts Single Relay REL-IR4/DP-220DC/4X21 2905728:

SpecValue
Product TypeSingle relay
Mechanical service lifeapprox. 2x 107 cycles
Nominal input voltage UN220 V DC
Input voltage range171.6 V DC ... 429 V DC

Phoenix 4 PDT Contacts Single Relay REL-IR4/DP-220DC/4X21, 2905728 Technical Specifications:

SpecificationValue
Product typeSingle relay
Mechanical service lifeapprox. 2x 107 cycles
InsulationBasic insulation
Overvoltage categoryII
Pollution degree2
Service life electricalsee diagram
Maximum power dissipation for nominal condition0.88 W
Test voltage (Winding/contact)2.5 kVrms (50 Hz, 1 min., winding/contact)
Test voltage (Changeover contact/changeover contact)2 kVrms (50 Hz, 1 min., changeover contact/changeover contact)
Rated insulation voltage250 V AC
Rated surge voltage2.5 kV
Nominal input voltage UN220 V DC
Input voltage range171.6 V DC ... 429 V DC
Drive and functionmonostable
Drive (polarity)polarized
Typical input current at UN4 mA
Typical response time14 ms
Coil voltage-
Status displayno
Contact switching type4 changeover contacts
Type of switch contactSingle contact
Contact materialAgNi
Maximum switching voltage250 V AC/DC
Minimum switching voltage5 V (At 24 mA)
Limiting continuous current6 A
Maximum inrush current-
Min. switching current5 mA (at 24 V)
Interrupting rating (ohmic load) max.144 W (at 24 V DC)
Connection methodPlug-in connection
Width21.2 mm
Height27.5 mm
Depth35.6 mm
Degree of protectionRT I
Degree of protection (Installation location)-
Ambient temperature (operation)70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Standards/regulationsIEC 60664
Mounting type-
Mounting positionany
Mains frequency-
Typical release time range-
Coil resistance-
Switching capacity2 A (at 24 V, DC13)
Motor load according to UL 508-
Input power dissipation for UN-
3-phase motor load-
Product family-
Relay type-
Test voltage ()-
Degree of protection (Relay)-
Inrush current, minimum-
Non-operate voltage≤ 132 V DC
Safe operate voltage≥ 176 V DC
Test voltage (N/O contact / N/O contact)-
Give Us a Call for Phoenix 4 PDT Contacts Single Relay REL-IR4/DP-220DC/4X21 part no: 2905728 at the lowest pricing. In-depth Technical Analysis of REL-IR4/DP-220DC/4X21, 2905728 feature mechanical service life of approx. 2x 107 cycles, designed for demanding industrial applications. The sensor operates at a nominal input voltage of 220 V DC, with an input voltage range of 171.6 V DC ... 429 V DC. The typical input current at UN is 4 mA with a response time of 13 ms. The sensor supports a maximum switching voltage of 250 V AC/DC, and a minimum switching voltage of 5 V (At 24 mA). It has a limiting continuous current of 6 A, with a maximum inrush current of -, and a minimum switching current of 5 mA (at 24 V). The interrupting rating for ohmic loads is 144 W (at 24 V DC). The connection method is via a Plug-in connection, with a degree of protection rated at RT I. The sensor operates reliably in ambient temperatures ranging from 70 °C. Elevate Your Project with a Quote for your requirement of Phoenix 4 PDT Contacts Single Relay. Our promise: More affordable pricing and more personalized support than other Distributors & Dealers.