Phoenix Single Phase TRIO Power TRIO-PS-2G/1AC/24DC/10, 2903149 Technical Specifications:
Specification
Value
Nominal input voltage range
110 V DC ... 250 V DC
Input voltage range
110 V DC ... 250 V DC -10 % ... +10 %
Inrush current
≤ 25 A (typical)
Efficiency
> 91 % (for 230 V AC and nominal values)
Nominal output voltage
24 V DC ±1 %
Nominal output current (IN)
10 A
Residual ripple
< 10 mVPP (with nominal values)
Short-circuit-proof
yes
Power loss nominal load max.
< 25 W
Insulation voltage input/output
3 kV AC (type test)
Mounting type
DIN rail mounting
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
EMC requirements for noise emission
EN 61000-6-3
EMC requirements for noise immunity
EN 61000-6-1
Get A Quote for Phoenix Single Phase TRIO Power TRIO-PS-2G/1AC/24DC/10 part no: 2903149 at the best price. Here are the brief Technical Specifications of TRIO-PS-2G/1AC/24DC/10, 2903149 are Operating within a nominal input voltage range of 110 V DC ... 250 V DC with a tolerance of 110 V DC ... 250 V DC -10 % ... +10 % this sensor ensures stable power delivery. With an efficiency greater than > 91 % (for 230 V AC and nominal values) it optimizes energy use. The sensor provides a nominal output voltage of 24 V DC ±1 % supporting a robust nominal output current of 10 A. The residual ripple is kept under 60 °C Derating: 2,5 %/K). It's Time to get a Quote for your requirement of Phoenix Single Phase TRIO Power. We guarantee unmatched pricing and unparalleled support compared to other Distributors.