ATV610U15N4: Schneider VFD For 2HP 3 Phase Motor
Technical Specifications of Schneider VFD For 2HP 3 Phase Motor ATV610U15N4:
Spec | Value |
---|---|
Mounting mode | Cabinet mount |
Output Voltage | <= power supply voltage |
Connector Type | 1 RJ45 (on the remote graphic terminal) for Modbus serial |
Relay Output Type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Schneider VFD For 2HP 3 Phase Motor ATV610U15N4 Technical Specifications:
Specification | Value |
---|---|
Mounting mode | Cabinet mount |
Height | 297 mm350 mm with EMC plate |
Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bitsAI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bitsAI2, AI3 software-configurable temperature probe or water level sensor |
Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
Range of product | Easy Altivar 610 |
Ambient air temperature for operation | -15…45 °C (without derating)45…60 °C (with derating factor) |
Communication port protocol | Modbus serial |
Operating position | Vertical +/- 10 degree |
Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog inputAQ1, AQ2: +/- 0.2 % for analog output |
Product destination | Asynchronous motorsSynchronous motors |
IP degree of protection | IP20 |
number of preset speeds | 16 preset speeds |
Line current | 5.7 A at 380 V (normal duty)4.8 A at 460 V (normal duty)3.1 A at 380 V (heavy duty)2.6 A at 460 V (heavy duty) |
Braking to standstill | By DC injection |
Number of Units in Package 2 | - |
Analogue input number | 3 |
Output voltage | <= power supply voltage |
Analogue output type | Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bitsSoftware-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Sampling duration | 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input5 ms +/- 1 ms (DI5, DI6)configurable - pulse input10 ms +/- 1 ms (AQ1, AQ2) - analog output |
Depth | 203 mm |
Acceleration and deceleration ramps | S, U or customizedLinear adjustable separately from 0.01 to 9000 s |
Product specific application | Fan, pump, compressor, conveyor |
Continuous output current | 4 A at 4 kHz for normal duty2.2 A at 4 kHz for heavy duty |
Apparent power | 3.8 kVA at 460 V (normal duty)2.1 kVA at 460 V (heavy duty) |
Product or component type | Variable speed drive |
Width | 145 mm |
Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
Maximum transient current | 4.4 A during 60 s (normal duty)3.3 A during 60 s (heavy duty) |
Physical interface | 2-wire RS 485 for Modbus serial |
EMC filter | Integrated conforming to IEC 61800-3 category C3 with 50 m |
Discrete input type | DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhmDI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output |
Ambient air temperature for storage | - |
Noise level | 55 dB conforming to 86/188/EEC |
Relay output number | 3 |
Discrete input logic | Positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1)Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1) |
Connector type | 1 RJ45 (on the remote graphic terminal) for Modbus serial |
Relay Output Type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Net Weight | 3.135 kg |
Motor power hp | 2 hp for normal duty1 hp for heavy duty |
Electrical connection | Control, screw terminal: 0.5...1.5 mm²Line side, screw terminal: 2.5...16 mm²Motor, screw terminal: 2.5...16 mm² |
Transmission frame | RTU for Modbus serial |
Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V ACRelay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DCRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V ACRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
Pollution degree | 2 conforming to IEC 61800-5-1 |
Analogue output number | 2 |
Switching frequency | 2...12 kHz adjustable |
Motor power kW | 1.5 kW for normal duty0.75 kW for heavy duty |
Supply frequency | 50...60 Hz +/-5 % |
Output frequency | 0.1…500 Hz |
Protection type | Thermal protection: motorMotor phase break: motorThermal protection: driveOverheating: driveOvercurrent between output phases and earth: driveOverload of output voltage: driveShort-circuit protection: driveMotor phase break: driveOvervoltages on the DC bus: driveLine supply overvoltage: driveLine supply undervoltage: driveLine supply phase loss: driveOverspeed: driveBreak on the control circuit: drive |
Type of cooling | Forced convection |
Obtain a Quote for Schneider VFD For 2HP 3 Phase Motor ATV610U15N4 at economical prices. Specifications Overview for ATV610U15N4 reveals Cabinet mount, it supports a height range of 297 mm350 mm with EMC plate. This sensor operates using the Modbus serial communication protocol, ensuring seamless integration with the Easy Altivar 610 system. The operating position is Vertical +/- 10 degree. It delivers continuous output <= power supply voltage and is ideal for applications such as Fan, pump, compressor, conveyor. With a continuous output current of 4 A at 4 kHz for normal duty2.2 A at 4 kHz for heavy duty, the sensor handles significant loads. It has an apparent power of 3.8 kVA at 460 V (normal duty)2.1 kVA at 460 V (heavy duty). The product features a 2-wire RS 485 for Modbus serial interface and 1 RJ45 (on the remote graphic terminal) for Modbus serial connector. The switching frequency is adjustable from 2...12 kHz adjustable, and it supports a supply frequency of 50...60 Hz +/-5 % with an output frequency range of 0.1…500 Hz. Take the First Step with a Quote for your requirement of Schneider VFD For 2HP 3 Phase Motor. Our commitment to better pricing and exceptional support sets us apart from other Competitors.