ATV630D30N4Z: Schneider 30 kW VFD
Technical Specifications of Schneider 30 kW VFD ATV630D30N4Z:
Spec | Value |
---|---|
Shock Resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Connection Type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial |
Motor Power KW | 30 kW (normal duty)22 kW (heavy duty) |
Switching Frequency | 2...12 kHz adjustable4...12 kHz with derating factor |
Schneider 30 kW VFD ATV630D30N4Z Technical Specifications:
Specification | Value |
---|---|
Maximum input current | 53.3 A |
Electrical connection | Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16Line side: screw terminal 25...50 mm²/AWG 4...AWG 1Motor: screw terminal 25...50 mm²/AWG 4...AWG 1 |
Power dissipation in W | Natural convection: 93 W at 380 V, switching frequency 4 kHzForced convection: 640 W at 380 V, switching frequency 4 kHz |
Overvoltage category | III |
Net weight | 25.8 kg |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Frequency resolution | Display unit: 0.1 HzAnalog input: 0.012/50 Hz |
Output voltage | <= power supply voltage |
Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Product or component type | Variable speed drive |
Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mARelay outputs R1A, R1B, R1C 30 V DC 3000 mARelay outputs R2A, R2C 250 V AC 5000 mARelay outputs R2A, R2C 30 V DC 5000 mARelay outputs R3A, R3C 250 V AC 5000 mARelay outputs R3A, R3C 30 V DC 5000 mA |
Nominal switching frequency | 4 kHz |
Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protectionInternal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
Maximum transient current | 67.7 A during 60 s (normal duty)69.5 A during 60 s (heavy duty) |
Relay output number | 3 |
Type of polarization | No impedance |
Product specific application | Process and utilities |
Volume of cooling air | 240 m3/h |
Connector type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial |
Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Method of access | Slave Modbus TCP |
Product destination | Asynchronous motorsSynchronous motors |
Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
Ambient air temperature for storage | -40…70 °C |
Motor power hp | 40 hp normal duty30 hp heavy duty |
Transmission rate | 10, 100 Mbits4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Maximum THDI | <48 % from 80...100 % of load conforming to IEC 61000-3-12 |
Height | 597 mm |
Type of cooling | Forced convection |
Motor power kW | 30 kW (normal duty)22 kW (heavy duty) |
Number of Units in Package 1 | 1 |
Physical interface | Ethernet2-wire RS 485 |
Switching frequency | 2...12 kHz adjustable4...12 kHz with derating factor |
Apparent power | 38.2 kVA at 480 V (normal duty)29.8 kVA at 480 V (heavy duty) |
Standards | UL 508CIEC 61800-3IEC 61800-3 environment 1 category C2EN/IEC 61800-3 environment 2 category C3IEC 61800-5-1IEC 61000-3-12IEC 60721-3IEC 61508IEC 13849-1 |
Operating position | Vertical +/- 10 degree |
Discrete input logic | Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1) |
Package 2 Length | - |
Range of product | Altivar Process ATV600 |
[Us] rated supply voltage | 380...480 V - 15...10 % |
Permissible temporary current boost | 1.1 x In during 60 s (normal duty)1.5 x In during 60 s (heavy duty) |
Marking | CE |
Analogue input number | 3 |
Asynchronous motor control profile | Variable torque standardOptimized torque modeConstant torque standard |
Enclosure mounting | With heat sink |
Isolation | Between power and control terminals |
Ambient air temperature for operation | -15…50 °C (without derating)50…60 °C (with derating factor) |
Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-61 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
Supply frequency | 50...60 Hz - 5...5 % |
Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
Analogue output number | 2 |
Pollution degree | 2 |
Request a quote for the Schneider 30 kW VFD ATV630D30N4Z at economical prices. This VFD, part of the Altivar Process ATV600 range, is ideal for process and utility applications. Key specifications include a maximum input current of 53.3 A and a frequency resolution of 0.1 Hz on the display unit, with 0.012/50 Hz on the analog input. The output voltage is up to the power supply voltage, with a maximum transient current of 67.7 A for 60 seconds in normal duty and 69.5 A in heavy duty. It supports motor power of 40 hp for normal duty and 30 hp for heavy duty, standing at a height of 597 mm and featuring Ethernet and a 2-wire RS 485 interface. The switching frequency is adjustable from 2...12 kHz, or 4...12 kHz with a derating factor. Operating at a rated supply voltage [Us] of 380...480 V with a -15...+10 % tolerance and a supply frequency of 50...60 Hz within -5...+5 % tolerance, it reaches a maximum output frequency of 500 kHz and is securely installed in a cabinet mount. Reach out now for a tailored quote on the Schneider 30 kW VFD and experience our competitive pricing and exceptional support, setting us apart from other competitors.