ATV630D90N4Z: Schneider Altivar Process ATV600 90kW VSD
Technical Specifications of Schneider Altivar Process ATV600 90kW VSD ATV630D90N4Z:
Spec | Value |
---|---|
Shock Resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Connection Type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial |
Motor Power KW | 90 kW (normal duty)75 kW (heavy duty) |
Switching Frequency | 2.5...8 kHz with derating factor2...8 kHz adjustable |
Schneider Altivar Process ATV600 90kW VSD ATV630D90N4Z Technical Specifications:
Specification | Value |
---|---|
Maximum input current | 156.2 A |
Electrical connection | Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16Line side: screw terminal 120 mm²/AWG 4/0...250 kcmilMotor: screw terminal 120 mm²/250 kcmil |
Power dissipation in W | Natural convection: 196 W at 380 V, switching frequency 2.5 kHzForced convection: 1585 W at 380 V, switching frequency 2.5 kHz |
Overvoltage category | III |
Net weight | 54.6 kg |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
Frequency resolution | Display unit: 0.1 HzAnalog input: 0.012/50 Hz |
Output voltage | <= power supply voltage |
Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Product or component type | Variable speed drive |
Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mARelay outputs R1A, R1B, R1C 30 V DC 3000 mARelay outputs R2A, R2C 250 V AC 5000 mARelay outputs R2A, R2C 30 V DC 5000 mARelay outputs R3A, R3C 250 V AC 5000 mARelay outputs R3A, R3C 30 V DC 5000 mA |
Nominal switching frequency | 2.5 kHz |
Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protectionInternal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
Maximum transient current | 190.3 A during 60 s (normal duty)217.5 A during 60 s (heavy duty) |
Relay output number | 3 |
Type of polarization | No impedance |
Product specific application | Process and utilities |
Volume of cooling air | 295 m3/h |
Connector type | RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial |
Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
Method of access | Slave Modbus TCP |
Product destination | Asynchronous motorsSynchronous motors |
Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output |
Ambient air temperature for storage | -40…70 °C |
Motor power hp | 125 hp normal duty100 hp heavy duty |
Transmission rate | 10, 100 Mbits4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
Maximum THDI | <48 % from 80...100 % of load conforming to IEC 61000-3-12 |
Height | 748 mm |
Type of cooling | Forced convection |
Motor power kW | 90 kW (normal duty)75 kW (heavy duty) |
Number of Units in Package 1 | 1 |
Physical interface | Ethernet2-wire RS 485 |
Switching frequency | 2.5...8 kHz with derating factor2...8 kHz adjustable |
Apparent power | 112.9 kVA at 480 V (normal duty)98.2 kVA at 480 V (heavy duty) |
Standards | UL 508CIEC 61800-3IEC 61800-3 environment 1 category C2EN/IEC 61800-3 environment 2 category C3IEC 61800-5-1IEC 61000-3-12IEC 60721-3IEC 61508IEC 13849-1 |
Operating position | Vertical +/- 10 degree |
Discrete input logic | Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1) |
Package 2 Length | - |
Range of product | Altivar Process ATV600 |
[Us] rated supply voltage | 380...480 V - 15...10 % |
Permissible temporary current boost | 1.1 x In during 60 s (normal duty)1.5 x In during 60 s (heavy duty) |
Marking | CE |
Analogue input number | 3 |
Asynchronous motor control profile | Constant torque standardVariable torque standardOptimized torque mode |
Enclosure mounting | With heat sink |
Isolation | Between power and control terminals |
Ambient air temperature for operation | -15…50 °C (without derating)50…60 °C (with derating factor) |
Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-61 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
Supply frequency | 50...60 Hz - 5...5 % |
Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
Analogue output number | 2 |
Pollution degree | 2 |
Obtain a Quote for Schneider Altivar Process ATV600 90kW VSD ATV630D90N4Z at economical prices. Specifications Overview for ATV630D90N4Z reveals Altivar Process ATV600 range, designed for Process and utilities applications. It has a maximum input current of 156.2 A, with a frequency resolution of Display unit: 0.1 HzAnalog input: 0.012/50 Hz. The output voltage is equal to or less than the <= power supply voltage, while the maximum transient current reaches 190.3 A during 60 s (normal duty)217.5 A during 60 s (heavy duty) operations. The sensor features a motor power of 125 hp normal duty100 hp heavy duty. Its height is 748 mm, and the physical interface includes Ethernet2-wire RS 485. The switching frequency is 2.5...8 kHz with derating factor2...8 kHz adjustable. It operates at a rated supply voltage [Us] of 380...480 V - 15...10 % with a supply frequency of 50...60 Hz - 5...5 %. The maximum output frequency is 500 kHz, with a Cabinet mount mode for secure installation. Take the First Step with a Quote for your requirement of Schneider Altivar Process ATV600 90kW VSD. Our commitment to better pricing and exceptional support sets us apart from other Competitors.