Technical Specifications of Schneider ATV630 Cabinet Integration VFD ATV630U22N4Z:

SpecValue
Shock Resistance15 gn for 11 ms conforming to IEC 60068-2-27
Connection TypeRJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial
Motor Power KW2.2 kW (normal duty)1.5 kW (heavy duty)
Switching Frequency2...12 kHz adjustable4...12 kHz with derating factor

Schneider ATV630 Cabinet Integration VFD ATV630U22N4Z Technical Specifications:

SpecificationValue
Maximum input current4.3 A
Electrical connectionControl: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16Motor: screw terminal 2.5...6 mm²/AWG 14...AWG 10Line side: screw terminal 2.5...6 mm²/AWG 14...AWG 10
Power dissipation in WNatural convection: 30 W at 380 V, switching frequency 4 kHzForced convection: 60 W at 380 V, switching frequency 4 kHz
Overvoltage categoryIII
Net weight3.7 kg
Shock resistance15 gn for 11 ms conforming to IEC 60068-2-27
Relay output typeConfigurable relay logic R1: fault relay NO/NC electrical durability 100000 cyclesConfigurable relay logic R2: sequence relay NO electrical durability 100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Frequency resolutionDisplay unit: 0.1 HzAnalog input: 0.012/50 Hz
Output voltage<= power supply voltage
Insulation resistance> 1 MOhm 500 V DC for 1 minute to earth
Product or component typeVariable speed drive
Discrete output typeRelay outputs R1A, R1B, R1C 250 V AC 3000 mARelay outputs R1A, R1B, R1C 30 V DC 3000 mARelay outputs R2A, R2C 250 V AC 5000 mARelay outputs R2A, R2C 30 V DC 5000 mARelay outputs R3A, R3C 250 V AC 5000 mARelay outputs R3A, R3C 30 V DC 5000 mA
Nominal switching frequency4 kHz
SupplyExternal supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protectionInternal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
Maximum transient current6 A during 60 s (heavy duty)6.2 A during 60 s (normal duty)
Relay output number3
Type of polarizationNo impedance
Product specific applicationProcess and utilities
Volume of cooling air38 m3/h
Connector typeRJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial
Refresh timeRelay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Method of accessSlave Modbus TCP
Product destinationAsynchronous motorsSynchronous motors
Minimum switching currentRelay output R1, R2, R3: 5 mA at 24 V DC
Accuracy+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Ambient air temperature for storage-40…70 °C
Motor power hp3 hp normal duty2 hp heavy duty
Transmission rate10, 100 Mbits4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Maximum THDI<48 % full load conforming to IEC 61000-3-12
Height285 mm
Type of coolingForced convection
Motor power kW2.2 kW (normal duty)1.5 kW (heavy duty)
Number of Units in Package 11
Physical interfaceEthernet2-wire RS 485
Switching frequency2...12 kHz adjustable4...12 kHz with derating factor
Apparent power3.2 kVA at 480 V (normal duty)2.4 kVA at 480 V (heavy duty)
StandardsUL 508CIEC 61800-3IEC 61800-3 environment 1 category C2EN/IEC 61800-3 environment 2 category C3IEC 61800-5-1IEC 61000-3-12IEC 60721-3IEC 61508IEC 13849-1
Operating positionVertical +/- 10 degree
Discrete input logicPositive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Package 2 Length60.000 cm
Range of productAltivar Process ATV600
[Us] rated supply voltage380...480 V - 15...10 %
Permissible temporary current boost1.1 x In during 60 s (normal duty)1.5 x In during 60 s (heavy duty)
MarkingCE
Analogue input number3
Asynchronous motor control profileConstant torque standardOptimized torque modeVariable torque standard
Enclosure mountingWith heat sink
IsolationBetween power and control terminals
Ambient air temperature for operation-15…50 °C (without derating)50…60 °C (with derating factor)
Vibration resistance1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-61 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Supply frequency50...60 Hz - 5...5 %
Acceleration and deceleration rampsLinear adjustable separately from 0.01...9999 s
Analogue output number2
Pollution degree2
Call us for Schneider ATV630 Cabinet Integration VFD ATV630U22N4Z at the best rates. Technical Attributes of ATV630U22N4Z are Altivar Process ATV600 range, designed for Process and utilities applications. It has a maximum input current of 4.3 A, with a frequency resolution of Display unit: 0.1 HzAnalog input: 0.012/50 Hz. The output voltage is equal to or less than the <= power supply voltage, while the maximum transient current reaches 6 A during 60 s (heavy duty)6.2 A during 60 s (normal duty) operations. The sensor features a motor power of 3 hp normal duty2 hp heavy duty. Its height is 285 mm, and the physical interface includes Ethernet2-wire RS 485. The switching frequency is 2...12 kHz adjustable4...12 kHz with derating factor. It operates at a rated supply voltage [Us] of 380...480 V - 15...10 % with a supply frequency of 50...60 Hz - 5...5 %. The maximum output frequency is 500 kHz, with a Cabinet mount mode for secure installation. Unlock Exclusive Pricing with a Quote for your requirement of Schneider ATV630 Cabinet Integration VFD. Trust in our ability to provide more advantageous pricing and dedicated support beyond other other Dealers.