LC1E1201M7: Schneider 12A Easy TeSys Contactor 220V AC 3P

Technical Specifications of Schneider 12A Easy TeSys Contactor 220V AC 3P LC1E1201M7:

SpecValue
Product Component TypeContactor
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
Power Dissipation Per Pole0.36 W AC-31.6 W AC-1
Tightening TorquePower circuit: 1.2 N.mControl circuit: 1.2 N.m

Schneider 12A Easy TeSys Contactor 220V AC 3P LC1E1201M7 Technical Specifications:

SpecificationValue
RangeEasy TeSys
Range of productEasy TeSys Control
Product or component typeContactor
Poles description3P
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current25 A (at <55 °C) at <= 440 V AC AC-1 for power circuit12 A (at <55 °C) at <= 440 V AC AC-3 for power circuit
[Uc] control circuit voltage220 V AC 50/60 Hz
Motor power kW3 kW at 220...230 V AC 50/60 Hz5.5 kW at 380...400 V5.5 kW at 415 V5.5 kW at 440 V7.5 kW at 500 V7.5 kW at 660...690 V
Pole contact composition3 NO
[Ith] conventional free air thermal current25 A (at 55 °C) for power circuit
Irms rated making capacity120 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity96 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current105 A 40 °C - 10 s for power circuit61 A 40 °C - 60 s for power circuit30 A 40 °C - 600 s for power circuit
Associated fuse rating10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-125 A gG at <= 690 V coordination type 1 for power circuit
Power dissipation per pole0.36 W AC-31.6 W AC-1
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage6 kV coil not connected to the power circuit conforming to IEC 60947
Control circuit typeAC at 50/60 Hz
Control circuit voltage limits0.85...1.1 Uc (-5…55 °C):operational 50/60 Hz0.3...0.6 Uc (-5…55 °C):drop-out 50/60 Hz
Inrush power in VA95 VA 50 Hz cos phi 0.75 (at 20 °C)95 VA 60 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA8.3 VA 50 Hz cos phi 0.3 (at 20 °C)8.5 VA 60 Hz cos phi 0.3 (at 20 °C)
Heat dissipation2…3 W for control circuit
Operating time12...22 ms on closing4...19 ms on opening
Maximum operating rate1800 cyc/h 60 °C
Connections - terminalsPower circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Tightening torquePower circuit: 1.2 N.mControl circuit: 1.2 N.m
Auxiliary contact composition1 NC
Minimum switching voltage17 V for control circuit
Minimum switching current5 mA for control circuit
Mounting supportPlateDIN rail
IP degree of protectionIP2X conforming to IEC 60529
Height74 mm
Width45 mm
Depth80 mm
Net weight0.3 kg
Please speak to our Technical Engineer for Schneider 12A Easy TeSys Contactor 220V AC 3P LC1E1201M7 at attractive prices. Technical Specs Summary of LC1E1201M7 includes Easy TeSys Control Range of products and the Contactor Product or component type 3P, designed for efficient performance in Power circuit: <= 690 V AC 50/60 Hz. This product features a rated operational current of 25 A (at <55 °C) at <= 440 V AC AC-1 for power circuit12 A (at <55 °C) at <= 440 V AC AC-3 for power circuit. It operates at a control circuit voltage of 220 V AC 50/60 Hz, with 3 NO poles. The conventional free air thermal current is rated at 25 A (at 55 °C) for power circuit, and power dissipation per pole is 0.36 W AC-31.6 W AC-1. The rated insulation voltage is 690 V conforming to IEC 60947-4-1, and the impulse withstand voltage is 6 kV coil not connected to the power circuit conforming to IEC 60947. Match Your Needs with a Quote for your requirement of Schneider 12A Easy TeSys Contactor 220V AC 3P. We lead with pricing that's more favorable and support that's more attentive than other Suppliers & Traders.