LC1E3810N5: Schneider 38A Easy TeSys 415V AC 3P Contactor
Technical Specifications of Schneider 38A Easy TeSys 415V AC 3P Contactor LC1E3810N5:
Spec | Value |
---|---|
Product Component Type | Contactor |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
Power Dissipation Per Pole | 2.9 W AC-35 W AC-1 |
Tightening Torque | Control circuit: 1.2 N.mPower circuit: 2.1 N.m |
Schneider 38A Easy TeSys 415V AC 3P Contactor LC1E3810N5 Technical Specifications:
Specification | Value |
---|---|
Range | Easy TeSys |
Range of product | Easy TeSys Control |
Product or component type | Contactor |
Poles description | 3P |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 50 A (at <55 °C) at <= 440 V AC AC-1 for power circuit38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit |
[Uc] control circuit voltage | 415 V AC 50 Hz |
Motor power kW | 18.5 kW at 500 V AC 50/60 Hz (AC-3)18.5 kW at 660...690 V AC 50/60 Hz (AC-3)9 kW at 220...230 V AC 50/60 Hz (AC-3)18.5 kW at 380...400 V AC 50/60 Hz (AC-3)18.5 kW at 415 V AC 50/60 Hz (AC-3)18.5 kW at 440 V AC 50/60 Hz (AC-3) |
Pole contact composition | 3 NO |
[Ith] conventional free air thermal current | 50 A (at 55 °C) |
Irms rated making capacity | 380 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
Rated breaking capacity | 304 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 60 A 40 °C - 600 s for power circuit310 A 40 °C - 10 s for power circuit150 A 40 °C - 60 s for power circuit |
Associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-163 A gG at <= 690 V coordination type 1 for power circuit |
Power dissipation per pole | 2.9 W AC-35 W AC-1 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
Control circuit type | AC at 50 Hz |
Control circuit voltage limits | 0.85...1.1 Uc (-5…55 °C):operational 50 Hz0.3...0.6 Uc (-5…55 °C):drop-out 50 Hz |
Inrush power in VA | 95 VA 50 Hz cos phi 0.75 (at 20 °C)95 VA 60 Hz cos phi 0.75 (at 20 °C) |
Hold-in power consumption in VA | 8.3 VA 50 Hz cos phi 0.3 (at 20 °C)8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
Heat dissipation | 2…3 W for control circuit |
Operating time | 12...22 ms on closing4...19 ms on opening |
Maximum operating rate | 1800 cyc/h 60 °C |
Connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end |
Tightening torque | Control circuit: 1.2 N.mPower circuit: 2.1 N.m |
Auxiliary contact composition | 1 NO |
Minimum switching voltage | 17 V for control circuit |
Minimum switching current | 5 mA for control circuit |
Mounting support | PlateDIN rail |
IP degree of protection | IP2X conforming to IEC 60529 |
Height | 84 mm |
Width | 56 mm |
Depth | 86 mm |
Net weight | 0.45 kg |
Send Your Inquiry for Schneider 38A Easy TeSys 415V AC 3P Contactor LC1E3810N5 with cost-effective solutions. Essential Technical Specs of LC1E3810N5 are Easy TeSys Control Range of products and the Contactor Product or component type 3P, designed for efficient performance in Power circuit: <= 690 V AC 50/60 Hz. This product features a rated operational current of 50 A (at <55 °C) at <= 440 V AC AC-1 for power circuit38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit. It operates at a control circuit voltage of 415 V AC 50 Hz, with 3 NO poles. The conventional free air thermal current is rated at 50 A (at 55 °C), and power dissipation per pole is 2.9 W AC-35 W AC-1. The rated insulation voltage is 690 V conforming to IEC 60947-4-1, and the impulse withstand voltage is 6 kV coil not connected to the power circuit conforming to IEC 60947. Capture the Best Deal with a Quote for your requirement of Schneider 38A Easy TeSys 415V AC 3P Contactor. Our pricing and support are designed to exceed the standards of other Traders & Suppliers.