LC1E630U7 | Schneider Easy TeSys Contactor 440V 630A 240V AC
+91 79955 44066 sales@indmall.in

LC1E630U7: Schneider Easy TeSys Contactor 440V 630A 240V AC

Technical Specifications of Schneider Easy TeSys Contactor 440V 630A 240V AC LC1E630U7:

SpecValue
Product Component TypeContactor
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
Power Dissipation Per Pole48 W AC-3120 W AC-1
Tightening TorqueControl circuit: 1.2 N.mPower circuit: 58 N.m

Schneider Easy TeSys Contactor 440V 630A 240V AC LC1E630U7 Technical Specifications:

SpecificationValue
RangeEasy TeSys
Range of productEasy TeSys Control
Product or component typeContactor
Poles description3P
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current630 A (at <55 °C) at <= 440 V AC AC-3 for power circuit1000 A (at <55 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage240 V AC 50/60 Hz
Motor power kW185 kW at 220...230 V AC 50/60 Hz335 kW at 380...400 V375 kW at 415 V400 kW at 440 V400 kW at 500 V450 kW at 660...690 V
Pole contact composition3 NO
[Ith] conventional free air thermal current1000 A (at 40 °C) for power circuit
Irms rated making capacity6300 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity5040 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current5050 A 40 °C - 10 s for power circuit
Associated fuse rating10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1800 A gG at <= 690 V coordination type 1 for power circuit
Power dissipation per pole48 W AC-3120 W AC-1
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage8 kV coil not connected to the power circuit conforming to IEC 60947
Control circuit typeAC at 50/60 Hz
Control circuit voltage limits0.85...1.1 Uc (-5…55 °C):operational 50/60 Hz0.25...0.5 Uc (-5…55 °C):drop-out 50/60 Hz
Inrush power in VA1650 VA 50 Hz cos phi 0.9 (at 20 °C)1650 VA 60 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA22 VA 50 Hz cos phi 0.9 (at 20 °C)22 VA 60 Hz cos phi 0.9 (at 20 °C)
Heat dissipation20 W for control circuit20 W
Operating time40...80 ms on closing100...200 ms on opening
Maximum operating rate1200 cyc/h 55 °C
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: cable with lug 2Power circuit: bars 2 - busbar cross section: 60 x 5 mm
Tightening torqueControl circuit: 1.2 N.mPower circuit: 58 N.m
Minimum switching voltage17 V for control circuit
Minimum switching current5 mA for control circuit
Mounting supportPlate
IP degree of protectionIP00 conforming to IEC 60529
Height304 mm
Width309 mm
Depth255 mm
Net weight18.6 kg
Give Us a Call for Schneider Easy TeSys Contactor 440V 630A 240V AC LC1E630U7 at the lowest pricing. In-depth Technical Analysis of LC1E630U7 feature Easy TeSys Control Range of products and the Contactor Product or component type 3P, designed for efficient performance in Power circuit: <= 690 V AC 50/60 Hz. This product features a rated operational current of 630 A (at <55 °C) at <= 440 V AC AC-3 for power circuit1000 A (at <55 °C) at <= 440 V AC AC-1 for power circuit. It operates at a control circuit voltage of 240 V AC 50/60 Hz, with 3 NO poles. The conventional free air thermal current is rated at 1000 A (at 40 °C) for power circuit, and power dissipation per pole is 48 W AC-3120 W AC-1. The rated insulation voltage is 690 V conforming to IEC 60947-4-1, and the impulse withstand voltage is 8 kV coil not connected to the power circuit conforming to IEC 60947. Elevate Your Project with a Quote for your requirement of Schneider Easy TeSys Contactor 440V 630A 240V AC. Our promise: More affordable pricing and more personalized support than other Distributors & Dealers.