Technical Specifications of Schneider 65A Easy TeSys 24V AC 3P Contactor LC1E65B7:
Spec | Value |
---|---|
Product Component Type | Contactor |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
Power Dissipation Per Pole | 4.2 W AC-36.4 W AC-1 |
Tightening Torque | Control circuit: 1.2 N.mPower circuit: 5 N.m |
Schneider 65A Easy TeSys 24V AC 3P Contactor LC1E65B7 Technical Specifications:
Specification | Value |
---|---|
Range | Easy TeSys |
Range of product | Easy TeSys Control |
Product or component type | Contactor |
Poles description | 3P |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 65 A (at <55 °C) at <= 440 V AC AC-3 for power circuit80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
[Uc] control circuit voltage | 24 V AC 50/60 Hz |
Motor power kW | 18.5 kW at 220...230 V AC 50/60 Hz30 kW at 380...400 V37 kW at 415 V37 kW at 440 V37 kW at 500 V37 kW at 660...690 V |
Pole contact composition | 3 NO |
[Ith] conventional free air thermal current | 80 A (at 55 °C) |
Irms rated making capacity | 650 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
Rated breaking capacity | 520 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 520 A 40 °C - 10 s for power circuit260 A 40 °C - 60 s for power circuit110 A 40 °C - 600 s for power circuit |
Associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1125 A gG at <= 690 V coordination type 1 for power circuit |
Power dissipation per pole | 4.2 W AC-36.4 W AC-1 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
Control circuit type | AC at 50/60 Hz |
Control circuit voltage limits | 0.85...1.1 Uc (-5…55 °C):operational 50/60 Hz0.3...0.6 Uc (-5…55 °C):drop-out 50/60 Hz |
Inrush power in VA | 160 VA 50 Hz cos phi 0.75 (at 20 °C)140 VA 60 Hz cos phi 0.75 (at 20 °C) |
Hold-in power consumption in VA | 15 VA 50 Hz cos phi 0.3 (at 20 °C)13 VA 60 Hz cos phi 0.3 (at 20 °C) |
Heat dissipation | 6…10 W for control circuit |
Operating time | 20...26 ms on closing8...12 ms on opening |
Maximum operating rate | 1200 cyc/h 60 °C |
Connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end |
Tightening torque | Control circuit: 1.2 N.mPower circuit: 5 N.m |
Auxiliary contact composition | 1 NO + 1 NC |
Minimum switching voltage | 17 V for control circuit |
Minimum switching current | 5 mA for control circuit |
Mounting support | PlateDIN rail |
IP degree of protection | IP2X conforming to IEC 60529 |
Height | 127 mm |
Width | 75 mm |
Depth | 114 mm |
Net weight | 0.98 kg |
Get A Quote for Schneider 65A Easy TeSys 24V AC 3P Contactor LC1E65B7 at the best price. Here are the brief Technical Specifications of LC1E65B7 are Easy TeSys Control Range of products and the Contactor Product or component type 3P, designed for efficient performance in Power circuit: <= 690 V AC 50/60 Hz. This product features a rated operational current of 65 A (at <55 °C) at <= 440 V AC AC-3 for power circuit80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit. It operates at a control circuit voltage of 24 V AC 50/60 Hz, with 3 NO poles. The conventional free air thermal current is rated at 80 A (at 55 °C), and power dissipation per pole is 4.2 W AC-36.4 W AC-1. The rated insulation voltage is 690 V conforming to IEC 60947-4-1, and the impulse withstand voltage is 6 kV coil not connected to the power circuit conforming to IEC 60947. It's Time to get a Quote for your requirement of Schneider 65A Easy TeSys 24V AC 3P Contactor. We guarantee unmatched pricing and unparalleled support compared to other Distributors.