LC1G5004LSEA | Schneider 200-500V Wide Band Contactor
+91 79955 44066 sales@indmall.in

LC1G5004LSEA: Schneider 200-500V Wide Band Contactor

Technical Specifications of Schneider 200-500V Wide Band Contactor LC1G5004LSEA:

SpecValue
Power Dissipation Per Pole40 W AC-1 - Ith 700 A20 W AC-3 - Ith 500 A
Range of ProductTeSys Giga
Pole Contact Composition4 NO
Connection TerminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end

Schneider 200-500V Wide Band Contactor LC1G5004LSEA Technical Specifications:

SpecificationValue
Device short nameLC1G
Power dissipation per pole40 W AC-1 - Ith 700 A20 W AC-3 - Ith 500 A
Ambient air temperature for operation-25…60 °C
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz<= 460 V DC
Range of productTeSys Giga
Rated breaking capacity4600 A at 440 V
Auxiliary contact composition1 NO + 1 NC
Maximum operating rate600 cyc/h AC-3600 cyc/h AC-3e300 cyc/h AC-1
Width185 mm
Poles description4P
Utilisation categoryAC-3AC-3eAC-1AC-5aAC-5bAC-6aAC-6bDC-1DC-3DC-5
ColourDark grey
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C)Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Motor power hp-
Height290 mm
Mechanical durability8 Mcycles
[Ie] rated operational current500 A (at <60 °C) at <= 440 V AC-3700 A (at <40 °C) at <= 1000 V AC-1
Operating time40...70 ms closing15...50 ms opening
Pole contact composition4 NO
Ambient air temperature for storage-60…80 °C
Product or component typeContactor
[Uc] control circuit voltage200...500 V AC 50/60 Hz200...500 V DC
Tightening torque35 N.m
Depth226 mm
Associated fuse rating500 A aM at <= 440 V for motor400 A aM at <= 690 V for motor800 A gG at <= 690 V
[Icw] rated short-time withstand current4.0 kA - 10 s2.8 kA - 30 s2.2 kA - 1 min1.5 kA - 3 min1.2 kA - 10 min
Motor power kW-
Net weight8.7 kg
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529IP2X front face with shrouds conforming to VDE 0106
hold-in power consumption in W (DC)8.6 W
RangeTeSys
Connections - terminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mmPower circuit: lugs-ring terminals 1 185 mm²Power circuit: bolted connectionControl circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable endControl circuit: push-in 2 0.5…1.0 mm² with cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable endControl circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
[Uimp] rated impulse withstand voltage8 kV
Mounting supportPlate
Connection pitch45 mm
[Ui] rated insulation voltage1000 V
Obtain a Quote for Schneider 200-500V Wide Band Contactor LC1G5004LSEA at economical prices. Specifications Overview for LC1G5004LSEA reveals device short name LC1G, designed for efficient power management in industrial applications. The sensor has a power dissipation per pole of 40 W AC-1 - Ith 700 A20 W AC-3 - Ith 500 A, ensuring energy-efficient operation. It operates within a broad ambient temperature range of -25…60 °C, making it suitable for various environmental conditions. The rated operational voltage [Ue] is up to <= 1000 V AC 50/60 Hz<= 460 V DC, providing robust power handling. Its rated breaking capacity reaches 4600 A at 440 V, ensuring reliable performance during switching. The auxiliary contact composition includes 1 NO + 1 NC, enhancing flexibility in control applications. With the mechanical durability of 8 Mcycles, the sensor guarantees long-lasting reliability. Operating times include a closing time of 40...70 ms closing15...50 ms opening quick and responsive operation. Take the First Step with a Quote for your requirement of Schneider 200-500V Wide Band Contactor. Our commitment to better pricing and exceptional support sets us apart from other Competitors.