LC1K0610F72 | Schneider TeSys K 6A Contactor 110VAC Coil
+91 79955 44066 sales@indmall.in

LC1K0610F72: Schneider TeSys K 6A Contactor 110VAC Coil

Technical Specifications of Schneider TeSys K 6A Contactor 110VAC Coil LC1K0610F72:

SpecValue
Power pole contact composition3 NO
Control Circuit TypeAC 50/60 Hz
Inrush power in W-
Connection Terminalsscrew clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end

Schneider TeSys K 6A Contactor 110VAC Coil LC1K0610F72 Technical Specifications:

SpecificationValue
RangeTeSys
Product or Component TypeContactor
Device short nameLC1K
Contactor applicationMotor control
Utilisation categoryAC-3AC-3eAC-4
Poles description3P
Power pole contact composition3 NO
[Ue] rated operational voltagePower circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz
[Ie] rated operational current6 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit6 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
Control circuit type [Uc]AC 50/60 Hz
Control circuit voltage110 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 140 °F (60 °C)) for power circuit10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity110 A AC for power circuit conforming to IEC 60947110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current90 A 122 °F (50 °C) - 1 s for power circuit85 A 122 °F (50 °C) - 5 s for power circuit80 A 122 °F (50 °C) - 10 s for power circuit60 A 122 °F (50 °C) - 30 s for power circuit45 A 122 °F (50 °C) - 1 min for power circuit40 A 122 °F (50 °C) - 3 min for power circuit20 A 122 °F (50 °C) - >= 15 min for power circuit80 A - 1 s for signalling circuit90 A - 500 ms for signalling circuit110 A - 100 ms for signalling circuit
Associated fuse rating25 A gG at <= 440 V for power circuit25 A aM for power circuit10 A gG for signalling circuit conforming to IEC 6094710 A gG for signalling circuit conforming to VDE 0660
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit 600 V UL 508Power circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-5-1Signalling circuit 600 V UL 508Power circuit 600 V CSA C22.2 No 14Signalling circuit 600 V CSA C22.2 No 14
Inrush power in W-
Hold-in power consumption in W-
Heat dissipation1.3 W
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <122 °F (50 °C))Drop-out: >= 0.20 Uc (at <122 °F (50 °C))
Connections - terminalsscrew clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end
Maximum operating rate3600 cyc/h
Mounting SupportPlateRail
Operating time10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing
Height2.3 in (58 mm)
Width1.8 in (45 mm)
Depth2.2 in (57 mm)
Net Weight0.40 lb(US) (0.18 kg)
IP degree of protectionIP2X VDE 0106
Ambient air temperature for operation-
Ambient Air Temperature for Storage-58…176 °F (-50…80 °C)
Operating altitude6561.68 ft (2000 m) without derating
Talk to Our Engineer for Schneider TeSys K 6A Contactor 110VAC Coil LC1K0610F72 with exclusive offers. Core System Specifications of LC1K0610F72 are Contactor Product or Component Type 3 NO power pole contact composition. This contactor operates with a rated operational voltage of up to Power circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz, ensuring flexibility in various industrial applications. The control circuit operates on a AC 50/60 Hz with a control voltage of 110 V AC 50/60 Hz, providing reliable control functionality. It has a rated impulse withstand voltage of 8 kV, conforming to industry standards for electrical safety. The compact design includes a height of 2.3 in (58 mm), a width of 1.8 in (45 mm), and a depth of 2.2 in (57 mm). Don't Miss Out on a Quote for your requirement of Schneider TeSys K 6A Contactor 110VAC Coil. Count on us for more economical pricing and more reliable support than other Dealers & Distributors.