Technical Specifications of Schneider Contactor With 3-Pole Coil LC1K0901P7:

SpecValue
[Uc] control circuit voltage230 V AC 50/60 Hz
Auxiliary Contact Composition1 NC
Mounting Support-
Inrush power in W-

Schneider Contactor With 3-Pole Coil LC1K0901P7 Technical Specifications:

SpecificationValue
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
[Uc] control circuit voltage230 V AC 50/60 Hz
Minimum switching voltage17 V for signalling circuit
contactor applicationResistive loadMotor control
Width45 mm
Control circuit typeAC at 50/60 Hz
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
Depth57 mm
[Ie] rated operational current9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Auxiliary contacts typetype instantaneous 1 NC
poles description3P
Auxiliary contact composition1 NC
IP degree of protection-
[Ui] rated insulation voltage-
Operating altitude2000 m without derating
Ambient air temperature for operation-
Power pole contact composition3 NO
Hold-in power consumption in W-
Ambient air temperature for storage-
Utilisation categoryAC-3AC-3eAC-1AC-4
Insulation resistance> 10 MOhm for signalling circuit
Heat dissipation1.3 W
Hold-in power consumption in VA4.5 VA (at 20 °C)
Net weight-
Minimum switching current5 mA for signalling circuit
Mounting support-
Operating time10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing
Rated breaking capacity110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947
Product or component typeContactor
Tightening torque-
Maximum operating rate3600 cyc/h
RangeTeSys
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 HzSignalling circuit: <= 690 V AC <= 400 Hz
Height58 mm
Motor power kW2.2 kW at 220...230 V AC 50/60 Hz AC-34 kW at 380...415 V AC 50/60 Hz AC-34 kW at 440/690 V AC 50/60 Hz AC-32.2 kW at 220...230 V AC 50/60 Hz AC-3e4 kW at 380...415 V AC 50/60 Hz AC-3e4 kW at 440/690 V AC 50/60 Hz AC-3e2.2 kW at 220...230 V AC 50/60 Hz AC-44 kW at 380...415 V AC 50/60 Hz AC-44 kW at 440/690 V AC 50/60 Hz AC-4
Inrush power in W-
[Uimp] rated impulse withstand voltage8 kV
Electrical durability1.3 Mcycles 9 A AC-3 at Ue <= 440 V1.3 Mcycles 9 A AC-3e at Ue <= 440 V0.16 Mcycles 20 A AC-1 at Ue <= 690 V0.02 Mcycles 54 A AC-4 at Ue <= 440 V
Device short name-
IndMALL Automation Dealing offers Schneider Contactor With 3-Pole Coil LC1K0901P7 at unbeatable prices. The Main Technical Parameters of LC1K0901P7 are control circuit voltage [Uc] operates at 230 V AC 50/60 Hz, with a minimum switching voltage of 17 V for signalling circuit, ensuring responsive operation. It is suitable for both motor Resistive loadMotor control applications. The control circuit type is AC at 50/60 Hz, and the auxiliary contacts are type instantaneous 1 NC configuration, providing reliable switching. The sensor features a 3P design and operates at altitudes up to 2000 m without derating, ensuring versatility across various environments. it is energy efficient. The utilization categories include AC-3AC-3eAC-1AC-4, making it suitable for a wide range of applications. Product or component type Contactor. Take the First Step with a Quote for your requirement of Schneider Contactor With 3-Pole Coil. Choose us for unparalleled pricing and support over other Dealers & Distributors.