LC1K09107F7: Schneider 9A TeSys K Contactor 110VAC Coil
Technical Specifications of Schneider 9A TeSys K Contactor 110VAC Coil LC1K09107F7:
Spec | Value |
---|---|
Power pole contact composition | 3 NO |
Control Circuit Type | AC 50/60 Hz |
Inrush power in W | - |
Connection Terminals | Faston terminals 2 0.1 in (2.8 mm)) Faston terminals 1 0.25 in (6.35 mm)) |
Schneider 9A TeSys K Contactor 110VAC Coil LC1K09107F7 Technical Specifications:
Specification | Value |
---|---|
Range | TeSys |
Product or Component Type | Contactor |
Device short name | LC1K |
Contactor application | Motor controlResistive load |
Utilisation category | AC-3AC-3eAC-1AC-4 |
Poles description | 3P |
Power pole contact composition | 3 NO |
[Ue] rated operational voltage | Power circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz |
[Ie] rated operational current | 9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuit |
Control circuit type [Uc] | AC 50/60 Hz |
Control circuit voltage | 110 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
Overvoltage category | III |
[Ith] conventional free air thermal current | 20 A (at 140 °F (60 °C)) for power circuit10 A (at 122 °F (50 °C)) for signalling circuit |
Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947110 A AC for signalling circuit conforming to IEC 60947 |
Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947 |
[Icw] rated short-time withstand current | 90 A 122 °F (50 °C) - 1 s for power circuit85 A 122 °F (50 °C) - 5 s for power circuit80 A 122 °F (50 °C) - 10 s for power circuit60 A 122 °F (50 °C) - 30 s for power circuit45 A 122 °F (50 °C) - 1 min for power circuit40 A 122 °F (50 °C) - 3 min for power circuit20 A 122 °F (50 °C) - >= 15 min for power circuit80 A - 1 s for signalling circuit90 A - 500 ms for signalling circuit110 A - 100 ms for signalling circuit |
Associated fuse rating | 25 A gG at <= 440 V for power circuit25 A aM for power circuit10 A gG for signalling circuit conforming to IEC 6094710 A gG for signalling circuit conforming to VDE 0660 |
Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
[Ui] rated insulation voltage | - |
Inrush power in W | - |
Hold-in power consumption in W | - |
Heat dissipation | 1.3 W |
Control circuit voltage limits | Operational: 0.8...1.15 Uc (at <122 °F (50 °C))Drop-out: >= 0.20 Uc (at <122 °F (50 °C)) |
Connections - terminals | Faston terminals 2 0.1 in (2.8 mm)) Faston terminals 1 0.25 in (6.35 mm)) |
Maximum operating rate | 3600 cyc/h |
Mounting Support | - |
Operating time | 10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing |
Height | 2.3 in (58 mm) |
Width | 1.8 in (45 mm) |
Depth | 2.2 in (57 mm) |
Net Weight | - |
IP degree of protection | - |
Ambient air temperature for operation | - |
Ambient Air Temperature for Storage | - |
Operating altitude | 6561.68 ft (2000 m) without derating |
Talk to Our Engineer for Schneider 9A TeSys K Contactor 110VAC Coil LC1K09107F7 with exclusive offers. Core System Specifications of LC1K09107F7 are Contactor Product or Component Type 3 NO power pole contact composition. This contactor operates with a rated operational voltage of up to Power circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz, ensuring flexibility in various industrial applications. The control circuit operates on a AC 50/60 Hz with a control voltage of 110 V AC 50/60 Hz, providing reliable control functionality. It has a rated impulse withstand voltage of 8 kV, conforming to industry standards for electrical safety. The compact design includes a height of 2.3 in (58 mm), a width of 1.8 in (45 mm), and a depth of 2.2 in (57 mm). Don't Miss Out on a Quote for your requirement of Schneider 9A TeSys K Contactor 110VAC Coil. Count on us for more economical pricing and more reliable support than other Dealers & Distributors.