Technical Specifications of Schneider 12A TeSys K Contactor 400VAC Coil LC1K1210Q7:

SpecValue
Power pole contact composition3 NO
Control Circuit TypeAC 50/60 Hz
Inrush power in W-
Connection Terminalsscrew clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end

Schneider 12A TeSys K Contactor 400VAC Coil LC1K1210Q7 Technical Specifications:

SpecificationValue
RangeTeSys
Product or Component TypeContactor
Device short nameLC1K
Contactor applicationMotor controlResistive load
Utilisation categoryAC-3AC-3eAC-1AC-4
Poles description3P
Power pole contact composition3 NO
[Ue] rated operational voltagePower circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz
[Ie] rated operational current12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuit
Control circuit type [Uc]AC 50/60 Hz
Control circuit voltage380...400 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 140 °F (60 °C)) for power circuit10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity144 A AC for power circuit conforming to IEC 60947110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current115 A 122 °F (50 °C) - 1 s for power circuit105 A 122 °F (50 °C) - 5 s for power circuit100 A 122 °F (50 °C) - 10 s for power circuit75 A 122 °F (50 °C) - 30 s for power circuit55 A 122 °F (50 °C) - 1 min for power circuit50 A 122 °F (50 °C) - 3 min for power circuit25 A 122 °F (50 °C) - >= 15 min for power circuit80 A - 1 s for signalling circuit90 A - 500 ms for signalling circuit110 A - 100 ms for signalling circuit
Associated fuse rating25 A gG at <= 440 V for power circuit25 A aM for power circuit10 A gG for signalling circuit conforming to IEC 6094710 A gG for signalling circuit conforming to VDE 0660
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit 600 V UL 508Power circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-5-1Signalling circuit 600 V UL 508Power circuit 600 V CSA C22.2 No 14Signalling circuit 600 V CSA C22.2 No 14
Inrush power in W-
Hold-in power consumption in W-
Heat dissipation1.3 W
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at <122 °F (50 °C))Drop-out: >= 0.20 Uc (at <122 °F (50 °C))
Connections - terminalsscrew clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end
Maximum operating rate3600 cyc/h
Mounting SupportPlateRail
Operating time10...20 ms coil de-energisation and NO opening10...20 ms coil energisation and NO closing
Height2.3 in (58 mm)
Width1.8 in (45 mm)
Depth2.2 in (57 mm)
Net Weight0.40 lb(US) (0.18 kg)
IP degree of protectionIP2X VDE 0106
Ambient air temperature for operation-
Ambient Air Temperature for Storage-58…176 °F (-50…80 °C)
Operating altitude6561.68 ft (2000 m) without derating
IndMALL Automation Dealing offers Schneider 12A TeSys K Contactor 400VAC Coil LC1K1210Q7 at unbeatable prices. The Main Technical Parameters of LC1K1210Q7 are Contactor Product or Component Type 3 NO power pole contact composition. This contactor operates with a rated operational voltage of up to Power circuit <= 690 V AC <= 400 HzSignalling circuit <= 690 V AC <= 400 Hz, ensuring flexibility in various industrial applications. The control circuit operates on a AC 50/60 Hz with a control voltage of 380...400 V AC 50/60 Hz, providing reliable control functionality. It has a rated impulse withstand voltage of 8 kV, conforming to industry standards for electrical safety. The compact design includes a height of 2.3 in (58 mm), a width of 1.8 in (45 mm), and a depth of 2.2 in (57 mm). Take the First Step with a Quote for your requirement of Schneider 12A TeSys K Contactor 400VAC Coil. Choose us for unparalleled pricing and support over other Dealers & Distributors.