LP4K09013BW3: Schneider NC 24V DC TeSys K Contactor
Technical Specifications of Schneider NC 24V DC TeSys K Contactor LP4K09013BW3:
Spec | Value |
---|---|
[Uc] control circuit voltage | 24 V DC |
Auxiliary Contact Composition | 1 NC |
Mounting Support | RailPlate |
Inrush power in W | 1.8 W (at 20 °C) |
Schneider NC 24V DC TeSys K Contactor LP4K09013BW3 Technical Specifications:
Specification | Value |
---|---|
Connections - terminals | Spring terminals 1 cable(s) 0.75…1.5 mm²solidSpring terminals 1 cable(s) 0.75…1.5 mm²flexible without cable endSpring terminals 2 cable(s) 0.75…1.5 mm²flexible without cable end |
[Uc] control circuit voltage | 24 V DC |
Minimum switching voltage | 17 V for signalling circuit |
contactor application | Motor controlResistive load |
Width | 45 mm |
Control circuit type | DC wide range |
Average impedance | 3 mOhm - Ith 16 A 50 Hz for power circuit |
Depth | 57 mm |
[Ie] rated operational current | 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit |
Auxiliary contacts type | type instantaneous 1 NC |
poles description | 3P |
Auxiliary contact composition | 1 NC |
IP degree of protection | IP2X |
[Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508Power circuit: 690 V conforming to IEC 60947-4-1Signalling circuit: 690 V conforming to IEC 60947-4-1Signalling circuit: 690 V conforming to IEC 60947-5-1Signalling circuit: 600 V conforming to UL 508Power circuit: 600 V conforming to CSA C22.2 No 14Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
Operating altitude | 2000 m without derating |
Ambient air temperature for operation | -25…50 °C |
Power pole contact composition | 3 NO |
Hold-in power consumption in W | 1.8 W at 20 °C |
Ambient air temperature for storage | -50…80 °C |
Utilisation category | AC-3AC-3eAC-1AC-4 |
Insulation resistance | > 10 MOhm for signalling circuit |
Heat dissipation | 1.8 W |
Hold-in power consumption in VA | - |
Net weight | 0.235 kg |
Minimum switching current | 5 mA for signalling circuit |
Mounting support | RailPlate |
Operating time | 10...20 ms coil de-energisation and NO opening30...40 ms coil energisation and NO closing |
Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947 |
Product or component type | Contactor |
Tightening torque | - |
Maximum operating rate | 3600 cyc/h |
Range | TeSys |
[Ue] rated operational voltage | Power circuit: <= 690 V AC <= 400 HzSignalling circuit: <= 690 V AC <= 400 Hz |
Height | 58 mm |
Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz AC-34 kW at 380...415 V AC 50/60 Hz AC-34 kW at 440/690 V AC 50/60 Hz AC-32.2 kW at 220...230 V AC 50/60 Hz AC-3e4 kW at 380...415 V AC 50/60 Hz AC-3e4 kW at 440/690 V AC 50/60 Hz AC-3e2.2 kW at 220...230 V AC 50/60 Hz AC-44 kW at 380...415 V AC 50/60 Hz AC-44 kW at 440/690 V AC 50/60 Hz AC-4 |
Inrush power in W | 1.8 W (at 20 °C) |
[Uimp] rated impulse withstand voltage | 8 kV |
Electrical durability | 1.3 Mcycles 9 A AC-3 at Ue <= 440 V1.3 Mcycles 9 A AC-3e at Ue <= 440 V0.16 Mcycles 20 A AC-1 at Ue <= 690 V0.02 Mcycles 54 A AC-4 at Ue <= 440 V |
Device short name | LP4K |
Please speak to our Technical Engineer for Schneider NC 24V DC TeSys K Contactor LP4K09013BW3 at attractive prices. Technical Specs Summary of LP4K09013BW3 includes control circuit voltage [Uc] operates at 24 V DC, with a minimum switching voltage of 17 V for signalling circuit, ensuring responsive operation. It is suitable for both motor Motor controlResistive load applications. The control circuit type is DC wide range, and the auxiliary contacts are type instantaneous 1 NC configuration, providing reliable switching. The sensor features a 3P design and operates at altitudes up to 2000 m without derating, ensuring versatility across various environments. Heat dissipation 1.3 W, it is energy efficient. The utilization categories include AC-3AC-3eAC-1AC-4, making it suitable for a wide range of applications. Product or component type Contactor. Match Your Needs with a Quote for your requirement of Schneider NC 24V DC TeSys K Contactor. We lead with pricing that's more favorable and support that's more attentive than other Suppliers & Traders.