LP4K0910BW3: Schneider 9A 3P Contactor With Coil

Technical Specifications of Schneider 9A 3P Contactor With Coil LP4K0910BW3:

SpecValue
[Uc] control circuit voltage24 V DC
Auxiliary Contact Composition1 NO
Mounting SupportPlateRail
Inrush power in W1.8 W (at 20 °C)

Schneider 9A 3P Contactor With Coil LP4K0910BW3 Technical Specifications:

SpecificationValue
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solidScrew clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable endScrew clamp terminals 2 cable(s) 1.5…4 mm²solidScrew clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable endScrew clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable endPower circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end
[Uc] control circuit voltage24 V DC
Minimum switching voltage17 V for signalling circuit
contactor applicationResistive loadMotor control
Width45 mm
Control circuit typeDC wide range
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
Depth57 mm
[Ie] rated operational current9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit
Auxiliary contacts typetype instantaneous 1 NO
poles description3P
Auxiliary contact composition1 NO
IP degree of protectionIP2X
[Ui] rated insulation voltagePower circuit: 600 V conforming to UL 508Power circuit: 690 V conforming to IEC 60947-4-1Signalling circuit: 690 V conforming to IEC 60947-4-1Signalling circuit: 690 V conforming to IEC 60947-5-1Signalling circuit: 600 V conforming to UL 508Power circuit: 600 V conforming to CSA C22.2 No 14Signalling circuit: 600 V conforming to CSA C22.2 No 14
Operating altitude2000 m without derating
Ambient air temperature for operation-25…50 °C
Power pole contact composition3 NO
Hold-in power consumption in W1.8 W at 20 °C
Ambient air temperature for storage-50…80 °C
Utilisation categoryAC-3AC-3eAC-1AC-4
Insulation resistance> 10 MOhm for signalling circuit
Heat dissipation1.8 W
Hold-in power consumption in VA-
Net weight0.235 kg
Minimum switching current5 mA for signalling circuit
Mounting supportPlateRail
Operating time10...20 ms coil de-energisation and NO opening30...40 ms coil energisation and NO closing
Rated breaking capacity110 A at 220...230 V conforming to IEC 60947110 A at 380...400 V conforming to IEC 60947110 A at 415 V conforming to IEC 60947110 A at 440 V conforming to IEC 6094780 A at 500 V conforming to IEC 6094770 A at 660...690 V conforming to IEC 60947
Product or component typeContactor
Tightening torque0.8…1.3 N.m - on screw clamp terminals Philips No 20.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
Maximum operating rate3600 cyc/h
RangeTeSys
[Ue] rated operational voltagePower circuit: <= 690 V AC <= 400 HzSignalling circuit: <= 690 V AC <= 400 Hz
Height58 mm
Motor power kW2.2 kW at 220...230 V AC 50/60 Hz AC-34 kW at 380...415 V AC 50/60 Hz AC-34 kW at 440/690 V AC 50/60 Hz AC-32.2 kW at 220...230 V AC 50/60 Hz AC-3e4 kW at 380...415 V AC 50/60 Hz AC-3e4 kW at 440/690 V AC 50/60 Hz AC-3e2.2 kW at 220...230 V AC 50/60 Hz AC-44 kW at 380...415 V AC 50/60 Hz AC-44 kW at 440/690 V AC 50/60 Hz AC-4
Inrush power in W1.8 W (at 20 °C)
[Uimp] rated impulse withstand voltage8 kV
Electrical durability1.3 Mcycles 9 A AC-3 at Ue <= 440 V1.3 Mcycles 9 A AC-3e at Ue <= 440 V0.16 Mcycles 20 A AC-1 at Ue <= 690 V0.02 Mcycles 54 A AC-4 at Ue <= 440 V
Device short nameLP4K
Get A Quote for Schneider 9A 3P Contactor With Coil LP4K0910BW3 at the best price. Here are the brief Technical Specifications of LP4K0910BW3 are control circuit voltage [Uc] operates at 24 V DC, with a minimum switching voltage of 17 V for signalling circuit, ensuring responsive operation. It is suitable for both motor Resistive loadMotor control applications. The control circuit type is DC wide range, and the auxiliary contacts are type instantaneous 1 NO configuration, providing reliable switching. The sensor features a 3P design and operates at altitudes up to 2000 m without derating, ensuring versatility across various environments. Heat dissipation 1.8 W, it is energy efficient. The utilization categories include AC-3AC-3eAC-1AC-4, making it suitable for a wide range of applications. Product or component type Contactor. It's Time to get a Quote for your requirement of Schneider 9A 3P Contactor With Coil. We guarantee unmatched pricing and unparalleled support compared to other Distributors.