LR9D5367 | Schneider TeSys LRD Thermal Overload Relays
+91 79955 44066 sales@indmall.in

LR9D5367: Schneider Overload Relay With Phase Failure Sensitivity

Technical Specifications of Schneider Overload Relay With Phase Failure Sensitivity LR9D5367:

SpecValue
RangeTeSys
Control TypeRed push-button: stopBlue push-button: reset
IP Degree ProtectionIP20 conforming to IEC 60529
Mounting SupportUnder contactorRail

Schneider Overload Relay With Phase Failure Sensitivity LR9D5367 Technical Specifications:

SpecificationValue
Device short nameLR9D
RangeTeSys
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height118 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping in 4 s +/- 20 % conforming to IEC 60947-4-1
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
Thermal overload classClass 10 conforming to IEC 60947-4-1
Network typeAC
Tripping threshold1.05 +/- 0.06 In alarm conforming to IEC 60947-4-11.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessVibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsULCSACCCUKCA
Depth125 mm
Width115 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range60…100 A
Tightening torqueAlarm circuit: 0.45 N.m - on screw clamp terminalsPower circuit: 18 N.m - on bars M8Control circuit: 1.2 N.m - on screw clamp terminals
Mounting supportUnder contactorRail
Relay applicationMotor protection
Net weight0.885 kg
Mail Us for your needs in Schneider Overload Relay With Phase Failure Sensitivity LR9D5367 with budget-friendly prices. The Main Technical Parameters of LR9D5367 include device short name LR9D, from the TeSys range. The product, known as TeSys LRDTeSys Deca, is designed for reliable thermal protection in motor control applications. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 118 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The auxiliary contact composition includes 1 NO + 1 NC, and it features a thermal overload Class 10 conforming to IEC 60947-4-1. It supports both AC network types. The control type consists of a Red push-button: stopBlue push-button: reset. Customize Your Experience with a Quote for your requirement of Schneider Overload Relay With Phase Failure Sensitivity. Experience the difference with our competitive pricing and superior support over other Suppliers.