LRD10L | Schneider Overload Relay With Auxiliary Contact
+91 79955 44066 sales@indmall.in

LRD10L: Schneider Overload Relay With Auxiliary Contact

Technical Specifications of Schneider Overload Relay With Auxiliary Contact LRD10L:

SpecValue
RangeTeSysTeSys Deca
Control TypeRed push-button: stopBlue push-button: reset
IP Degree ProtectionIP20 conforming to IEC 60529
Mounting SupportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor

Schneider Overload Relay With Auxiliary Contact LRD10L Technical Specifications:

SpecificationValue
Device short nameLRD
RangeTeSysTeSys Deca
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height66 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Thermal overload classClass 20 conforming to IEC 60947-4-1
Network typeACDC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessShocks: 15 Gn for 11 ms conforming to IEC 60068-2-7Vibrations: 3 GN conforming to IEC 60068-2-6
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSAEACABSATEX INERISUKCA
Permissible current3 A at 120 V AC-15 for signalling circuit0.22 A at 125 V DC-13 for signalling circuit
Depth76 mm
Width45 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range4…6 A
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 1.7 N.m - on screw clamp terminals
Mounting supportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor
Relay applicationMotor protection
Net weight0.144 kg
Talk to Our Engineer for Schneider Overload Relay With Auxiliary Contact LRD10L with exclusive offers. Core System Specifications of LRD10L are device short name LRD, from the TeSysTeSys Deca range. The product, known as TeSys LRDTeSys Deca, is designed for reliable thermal protection in motor control applications. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 66 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The auxiliary contact composition includes 1 NO + 1 NC, and it features a thermal overload Class 20 conforming to IEC 60947-4-1. It supports both ACDC network types. The control type consists of a Red push-button: stopBlue push-button: reset. Don't Miss Out on a Quote for your requirement of Schneider Overload Relay With Auxiliary Contact. Count on us for more economical pricing and more reliable support than other Dealers & Distributors.