Technical Specifications of Schneider Class 10A Thermal Overload Relays LRD143:

SpecValue
RangeTeSysTeSys Deca
Control TypeRed push-button: stopBlue push-button: reset
IP Degree ProtectionIP20 conforming to IEC 60529
Mounting SupportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor

Schneider Class 10A Thermal Overload Relays LRD143 Technical Specifications:

SpecificationValue
Device short nameLRD
RangeTeSysTeSys Deca
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height93 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Thermal overload classClass 10A conforming to IEC 60947-4-1
Network typeACDC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSACCCEACBVRINADNV-GLLROS (Lloyds register of shipping)ATEX INERISUKCA
Permissible current3 A at 120 V AC-15 for signalling circuit0.22 A at 125 V DC-13 for signalling circuit
Depth72 mm
Width45 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range7…10 A
Flame retardanceV1 conforming to UL 94
Mounting supportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor
Relay applicationMotor protection
Net weight0.14 kg
Mail Us for your needs in Schneider Class 10A Thermal Overload Relays LRD143 with budget-friendly prices. The Main Technical Parameters of LRD143 include device short name LRD, from the TeSysTeSys Deca range. The product, known as TeSys LRDTeSys Deca, is designed for reliable thermal protection in motor control applications. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 93 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The auxiliary contact composition includes 1 NO + 1 NC, and it features a thermal overload Class 10A conforming to IEC 60947-4-1. It supports both ACDC network types. The control type consists of a Red push-button: stopBlue push-button: reset. Customize Your Experience with a Quote for your requirement of Schneider Class 10A Thermal Overload Relays. Experience the difference with our competitive pricing and superior support over other Suppliers.