LRD1516: Schneider TeSys LRD Thermal Overload Relays
Technical Specifications of Schneider TeSys LRD Thermal Overload Relays LRD1516:
Spec | Value |
---|---|
Range | TeSys |
Control Type | Red push-button: stopBlue push-button: reset |
IP Degree Protection | IP20 conforming to IEC 60529 |
Mounting Support | Plate, with specific accessoriesRail, with specific accessoriesUnder contactor |
Schneider TeSys LRD Thermal Overload Relays LRD1516 Technical Specifications:
Specification | Value |
---|---|
Device short name | LRD |
Range | TeSys |
Product name | TeSys LRDTeSys Deca |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
IP degree of protection | IP20 conforming to IEC 60529 |
Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
Temperature compensation | -20…60 °C |
Auxiliary contact composition | 1 NO + 1 NC |
[Uimp] rated impulse withstand voltage | 6 kV |
Thermal overload class | Class 20 conforming to IEC 60947-4-1 |
Network type | DCAC |
Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Control type | Red push-button: stopBlue push-button: reset |
Mechanical robustness | Vibrations: 6 Gn conforming to IEC 60068-2-6Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 |
[Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
Associated fuse rating | 4 A gG for signalling circuit4 A BS for signalling circuit |
Product certifications | IECULCSAEACDNV-GLLROS (Lloyds register of shipping)UKCA |
Permissible current | 1.5 A at 240 V AC-15 for signalling circuit0.1 A at 250 V DC-13 for signalling circuit |
Depth | 92 mm |
Width | 45 mm |
Ambient air temperature for storage | -60…70 °C |
Climatic withstand | conforming to IACS E10 |
Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
Thermal protection adjustment range | 9…13 A |
Flame retardance | V1 conforming to UL 94 |
Tightening torque | Control circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 1.85 N.m - on screw clamp terminals |
Mounting support | Plate, with specific accessoriesRail, with specific accessoriesUnder contactor |
Relay application | Motor protection |
Net weight | 0.19 kg |
IndMALL Automation Dealing offers Schneider TeSys LRD Thermal Overload Relays LRD1516 at unbeatable prices. The Main Technical Parameters of LRD1516 are device short name LRD, from the TeSys range. The product, known as TeSys LRDTeSys Deca, is designed for reliable thermal protection in motor control applications. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The auxiliary contact composition includes 1 NO + 1 NC, and it features a thermal overload Class 20 conforming to IEC 60947-4-1. It supports both DCAC network types. The control type consists of a Red push-button: stopBlue push-button: reset. Take the First Step with a Quote for your requirement of Schneider TeSys LRD Thermal Overload Relays. Choose us for unparalleled pricing and support over other Dealers & Distributors.