LRD22L: Schneider Electric Overload Relays With IP20 Protection
Technical Specifications of Schneider Electric Overload Relays With IP20 Protection LRD22L:
Spec | Value |
---|---|
Range | TeSysTeSys Deca |
Control Type | Red push-button: stopBlue push-button: reset |
IP Degree Protection | IP20 conforming to IEC 60529 |
Mounting Support | Plate, with specific accessoriesRail, with specific accessoriesUnder contactor |
Schneider Electric Overload Relays With IP20 Protection LRD22L Technical Specifications:
Specification | Value |
---|---|
Device short name | LRD |
Range | TeSysTeSys Deca |
Product name | TeSys LRDTeSys Deca |
[Ith] conventional free air thermal current | 5 A for signalling circuit |
Height | 66 mm |
IP degree of protection | IP20 conforming to IEC 60529 |
Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
Temperature compensation | -20…60 °C |
Auxiliary contact composition | 1 NO + 1 NC |
[Uimp] rated impulse withstand voltage | 6 kV |
Thermal overload class | Class 20 conforming to IEC 60947-4-1 |
Network type | ACDC |
Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Control type | Red push-button: stopBlue push-button: reset |
Mechanical robustness | Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7Vibrations: 3 GN conforming to IEC 60068-2-6 |
[Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
Associated fuse rating | 4 A gG for signalling circuit4 A BS for signalling circuit |
Product certifications | IECULCSAEACABSATEX INERISUKCA |
Permissible current | 3 A at 120 V AC-15 for signalling circuit0.22 A at 125 V DC-13 for signalling circuit |
Depth | 76 mm |
Width | 45 mm |
Ambient air temperature for storage | -60…70 °C |
Climatic withstand | conforming to IACS E10 |
Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
Thermal protection adjustment range | 17…24 A |
Tightening torque | Control circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 2.5 N.m - on screw clamp terminals |
Mounting support | Plate, with specific accessoriesRail, with specific accessoriesUnder contactor |
Relay application | Motor protection |
Net weight | 0.144 kg |
Mail Us for your needs in Schneider Electric Overload Relays With IP20 Protection LRD22L with budget-friendly prices. The Main Technical Parameters of LRD22L include device short name LRD, from the TeSysTeSys Deca range. The product, known as TeSys LRDTeSys Deca, is designed for reliable thermal protection in motor control applications. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 66 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The auxiliary contact composition includes 1 NO + 1 NC, and it features a thermal overload Class 20 conforming to IEC 60947-4-1. It supports both ACDC network types. The control type consists of a Red push-button: stopBlue push-button: reset. Customize Your Experience with a Quote for your requirement of Schneider Electric Overload Relays With IP20 Protection. Experience the difference with our competitive pricing and superior support over other Suppliers.