LRD318 | Schneider Electric Class 10A Overload Protection
+91 79955 44066 sales@indmall.in

LRD318: Schneider Electric Class 10A Overload Protection

Technical Specifications of Schneider Electric Class 10A Overload Protection LRD318:

SpecValue
RangeTeSysTeSys Deca
Control TypeRed push-button: stopBlue push-button: reset
IP Degree ProtectionIP20 conforming to IEC 60529
Mounting SupportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor

Schneider Electric Class 10A Overload Protection LRD318 Technical Specifications:

SpecificationValue
Device short nameLRD
RangeTeSysTeSys Deca
Product nameTeSys LRDTeSys Deca
[Ith] conventional free air thermal current5 A for signalling circuit
Height70 mm
IP degree of protectionIP20 conforming to IEC 60529
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Temperature compensation-20…60 °C
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV
Thermal overload classClass 10A conforming to IEC 60947-4-1
Network typeDCAC
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Control typeRed push-button: stopBlue push-button: reset
Mechanical robustnessShocks: 15 Gn for 11 ms conforming to IEC 60068-2-7Vibrations: 4 gn conforming to IEC 60068-2-6
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit4 A BS for signalling circuit
Product certificationsIECULCSACCCEACDNV-GLRMRSEU-RO MRLROS (Lloyds register of shipping)ATEX INERISUKCA
Permissible current0.95 A at 380 V AC-15 for signalling circuit0.06 A at 440 V DC-13 for signalling circuit
Depth123 mm
Width55 mm
Ambient air temperature for storage-60…70 °C
Climatic withstandconforming to IACS E10
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
Thermal protection adjustment range12…18 A
Flame retardanceV1 conforming to UL 94
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminalsPower circuit: 5 N.m - on EverLink BTR screw connectors
Mounting supportPlate, with specific accessoriesRail, with specific accessoriesUnder contactor
Relay applicationMotor protection
Net weight0.375 kg
Get A Quote for Schneider Electric Class 10A Overload Protection LRD318 at the best price. Here are the brief Technical Specifications of LRD318 are device short name LRD, from the TeSysTeSys Deca range. The product, known as TeSys LRDTeSys Deca, is designed for reliable thermal protection in motor control applications. It has a conventional free air thermal current [Ith] of 5 A for signalling circuit, making it suitable for demanding environments. With a height of 70 mm and an IP20 conforming to IEC 60529, it provides protection against solid objects. The sensor operates efficiently in ambient temperatures ranging from -20…60 °C, with temperature compensation to maintain performance. The auxiliary contact composition includes 1 NO + 1 NC, and it features a thermal overload Class 10A conforming to IEC 60947-4-1. It supports both DCAC network types. The control type consists of a Red push-button: stopBlue push-button: reset. It's Time to get a Quote for your requirement of Schneider Electric Class 10A Overload Protection. We guarantee unmatched pricing and unparalleled support compared to other Distributors.